12
www.ramsetinc.com
RAMSET
R
AM 3
000 U
L
- 3100 U
L
- 3200 U
L
DIP SWITCH "B"
DIP SWITCH CONFIGURATION
DIP SWITCH "A"
Dip Switch "A" 1, 2 & 3; AUTOMATIC TIMER TO CLOSE GATE
‘0’ is “OFF” ‘1’ is “ON”
Switch
1 2 3
Gate Open Duration:
1 1 1
60 seconds
1 1 0
45 seconds
1 0 1
30 seconds
1 0 0
15 seconds
0 1 1
10 seconds
0 1 0
05 seconds
0 0 1
00 seconds
0 0 0
disabled - command required to close
Dip Switch "A" 4; 1/2 HP E.R.D.
Sw. Function:
OFF Most
sensitive.
ON
Setting for stronger E.R.D. (Less sensitive)
Dip Switch "B" 1; Not in use at this time.
Leave in the ‘Off’ position.
Dip Switch "B" 2; “PREWARN”
Sw.
Pre Warning Relay:
OFF Normal
Operation
ON
Adds a 3-second delay before the gate moves in
any direction. During This 3 second delay the
PREWARN Relay maintains a closed contact.
Dip Switch "B" 3; “CONSTANT WARN”
(Constant warning when gate is in motion).
Sw. Function:
OFF No
effect.
ON
Triggers the prewarn relay to maintain a closed
contact while gate is in motion.
Dip Switch "B" 6; Not in use at this time.
Leave in the ‘Off’ position.
Dip Switch "B" 7; Not in use at this time.
Leave in the ‘Off’ position.
Dip Switch "B" 8; 3/4 HP E.R.D.
Sw. Function:
OFF “Low” E.R.D. for 3/4 hp motors (Most sensitive)
ON
“High” E.R.D. for 3/4 hp motors (Less sensitive)
Dip Switch "B" 4 & 5; “ADDRESS 1 & ADDRESS 0”
Up to four separate entrance addresses are available for
installations with multiple entrance or exit locations. Master and
slave gates that work together should be set to the same
address. (Side gates use the address setup)
Sw. 4 5 Function:
0 0 Default - Entrance 1
0 1 Entrance 2
1 0 Entrance 3
1 1 Entrance 4
"Intelligate" Control Board
Figure 13
R_Ramset_Ram3000.qxd 8/19/05 4:57 PM Page 14