background image

HEARTH REQUIREMENTS 

When using the Insert 60 in the Fireplace Insert Enclo-
sure, the hearth protection requirements are different than 
when installing the Insert 60 in an existing masonry fire-
place.  The enclosure has been designed to elevate the 
Insert 60 to the minimum distance above the combustible 
floor where no thermal floor protection is required.  How-
ever, unless the Insert 60 Fireplace Insert Enclosure will 
be installed on a completely non-combustible surface 
such as unpainted concrete over earth, spark and ember 
floor protection must be provided in front of the insert and 
enclosure.  This will protect the combustible floor in front 
of the load door from spilled coals or embers.  
 
The floor protector can be made from any completely 
non-combustible material such as galvanized steel or 
non-combustible tile backer board.  These materials may 
be covered with decorative non-combustible materials 
such as ceramic tile.  Other non-combustible materials 
may be used if there are no gaps or joints between pieces 
that would allow coals or embers to reach the combustible 
floor underneath.  Floor protectors meeting the require-
ments of UL-1618 Type 1 are acceptable. 
 
The floor protector must extend at least 8” (203mm) from 
the sides of the firebox opening making the minimum total 
width of the floor protector 34 ½ “ (875mm).  In addition, 
the floor protector must extend a minimum of 
16” (406mm) in front of the door opening in the United 
States and 18” (457mm) in Canada.  See Fig. 8. 
 
In addition, a 3” X 34 ½” (76mm X 875 mm) sheet metal 
spark protector strip must be laid under the junction be-
tween the front of the enclosure and the floor protector to 
prevent coals or embers from reaching the combustible 
floor.  See Fig. 7 on page 5. 

 

COMBUSTIBLE MANTEL 

A combustible mantel and any associated trim may be 
mounted to the wall above the Insert 60.  The mantel (or 
trim) must be a minimum of 24 1/4”  (616mm) above the 
top flange on the Insert 60.  See Fig. 9.  The mantel may 
not be deeper than 12” (305mm). 
 

CUSTOMIZING THE FINISHED  
APPEARANCE 

The facing of the Fireplace Insert Enclosure may be fin-
ished to give a variety of different aesthetic appearances.  
However, only non-combustible materials may be applied 
to the face inside the specified limits for combustible ma-
terials.  See Fig 6 on page 5. Outside the combustible 
limits, any surface finish may be used. 
 
For a smooth wall appearance, non-combustible tile 

24 1/4”  
(616mm) 

12” (305mm) 
Max. Depth 

FIG. 9 

backer board may be used as a base for plaster al-
lowing a seamless transition beyond the combustible 
limits to traditional wallboard. 
 
For tile, veneer brick or stone, the finish material may 
be applied over non-combustible tile backer board.  
The requirements for the facing material applied in-
side the combustible limits are: 
 



The material must be non-combustible. 



The total thickness, including non-combustible 
backer board and adhesive should not exceed 
13/16” (20mm). 



Facing materials should not encroach into the 
front opening in the enclosure in order to allow 
proper insertion of the Insert 60. 



Combustible trim at the transition to combustible 
facing material must not protrude into the room 
more than ¾” (19mm) from the facing material. 

L = 34 1/2” (875mm) Min. 
M = 16” (405 mm) Min. USA 
M = 18” (457mm) Min. Canada 
N = 8” (203mm) Min. 

FIG. 8 

DOOR OPENING 

Summary of Contents for INSERT 60

Page 1: ...IS A S Industrivej 20 9900 Frederikshavn Denmark TEL 45 98 47 90 33 RAIS Inc 1011 Highway 52 West Portland TN 37148 USA TEL 615 325 1700 INSTALLER Leave this manual with the appliance CONSUMER Retain...

Page 2: ...D FUEL BURNING APPLIANCES OR IN CANADA CSA B365 REFER TO THE RAIS INSERT 60 OPERATING IN STRUCTIONS FOR INFORMATION ON THE PROPER USE AND MAINTENANCE OF THE INSERT 60 FIRE PLACE INSERT REFER TO THE RA...

Page 3: ...us SDP In Canada the Insert 60 Fireplace Insert Enclosure is listed for use with any 150mm diameter chimney sys tem tested and listed to the High Temperature 650 C Chimney Standard ULC S 629 NOTE THE...

Page 4: ...installed can be slid into the rough open ing Make any last adjustments to center the enclosure in the opening and secure in place with at least four nails using the pilot holes provide in the enclosu...

Page 5: ...FIG 5 D F E G H J Combustible Non Combustible Material Limits E 39 3 8 1000mm F 60 3 4 1543mm G 28 3 4 730mm H 24 1 4 616 mm J 25 5 8 651mm K 10 7 8 276mm K Non Combustible Materials Only FIG 5 FIG 6...

Page 6: ...tector strip must be laid under the junction be tween the front of the enclosure and the floor protector to prevent coals or embers from reaching the combustible floor See Fig 7 on page 5 COMBUSTIBLE...

Page 7: ...and should be handled carefully to avoid damage 3 Remove the fireplace insert lining to provide access to the leveling screws Install the Insert 60 into the Fireplace Insert Enclosure 1 Using a helpe...

Page 8: ...8...

Reviews: