
ENGLISH RAIS - manual for RAIS 800
8
Chimney
The chimney is the driving force which makes the stove function. In order for the stove to
perform satisfactorily the chimney height must be sufficient to ensure the correct draught
of 14 to 18 Pa so as to clear the products of combustion and prevent problems of smoke
emanating into the room when firing.
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet
of the stove to the top of the chimney should be satisfactory. Alternatively the calcula-
tion procedure given in BS 5854:1980 may be used as the basis for deciding whether a
particular chimney design will provide sufficient draught.
The outlet from the chimney should be above the roof of the building in accordance with
the provisions of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no cracks or
other faults which might allow fumes into the house. Older properties, especially, may
have chimney faults or the cross section may be too large i.e. more than 230 mm x 230
mm. Remedial action should be taken, if required, seeking expert advice, if necessary. If it
is found necessary to line the chimney then a flue liner suitable for solid fuel must be used
in accordance with Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immedi-
ately before installation of the stove. If the stove is fitted in place of an open fire then the
chimney should be swept one month after installation to clear any soot falls which may
have occurred due to the difference in combustion between the stove and the open fire.
If there is no existing chimney then either a prefabricated block chimney in accordance
with Building Regulations Approved Document J or a twin walled insulated stainless steel
flue to BS 4543 can be used. These chimneys must be fitted in accordance with the manu-
facturer’s instructions and Building Regulations.
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not
suitable for using for the complete chimney. The chimney and connecting fluepipe must
have a minimum diameter of 150 mm and its dimension should be not less than the size
of the outlet socket of the stove which is 150 mm in diameter. Any bend in the chimney
or connecting fluepipe should not exceed 45°. 90°bends should not be used.
Combustible material should not be located where the heat dissipating through the walls
of fireplaces or flues could ignite it. Therefore when installing the stove in the presence
of combustible materials due account must be taken of the guidance on the separation
of combustible material given in Building Regulations Approved Document J and also in
these stove instructions.
Summary of Contents for 800
Page 1: ...ENGLISH RAIS manual for RAIS 800 1 U S E R M A N U A L RAIS 800...
Page 2: ...We cannot be held responsible for any misprints...
Page 29: ...ENGLISH RAIS manual for RAIS 800 29 1 2 3 4...
Page 30: ...ENGLISH RAIS manual for RAIS 800 30...
Page 31: ...ENGLISH RAIS manual for RAIS 800 31...
Page 32: ...RAIS A S Industrivej 20 DK 9900 Frederikshavn www rais dk...