background image

amount of backpressure needed to close 
the diaphragm.

5.  Turn off water supply and remove bonnet 

for possible debris or damage causing the 
diaphragm to stick open.

Leakage.

1.  Disassemble parts and inspect  

o-rings/sealing surfaces for damage.  
Check replacement parts exploded view 
for missing or replacement parts.

Accessories or persistent problems.

1.  Refer to the appropriate installation and 

operation manual for specific trouble-
shooting procedures

2.  Inside the US, please call the Rain Bird Spec 

Hotline at (800) 458-3005.

3.  Outside the US, please refer to the back 

page for contact information.

4.  Always visit us at www.rainbird.com.

Thank you for purchasing a Rain Bird G4 
Solenoid. This solenoid assembly is compat-
ible with the following Rain Bird valves: PGA, 
PEB, PESB, EFB-CP, and BPES.

To use this guide, fold out the back page for 
visual reference then turn to the appropriate 
language. Follow the alphanumeric referenc-
es for installation, adjustment, troubleshoot-
ing and replacement parts. Specifications can 
be found on the back of the foldout page.

Installation

  Refer to F1.

1.  WARNING: Turn off water supply and dis-

connect all electrical power sources.

2.  Turn the solenoid counter-clockwise to 

remove the G4 Solenoid.

l

B

  

3.  If desired, use an open-ended wrench to 

counter-clockwise remove the solenoid 
adapter.

l

C

  Clockwise replace solenoid 

adapter into valve bonnet 

l

D

  ensuring 

the o-ring does not become pinched or 
damaged.

4.  Clockwise thread replacement solenoid 

l

B

  into the solenoid adapter.

l

C

 

5.  Clockwise tighten the solenoid.

l

B

  

6.  Connect one solenoid wire 

l

A

  to the 

controller common wire and the other 
solenoid wire to the controller power 
wire.  Tighten and protect using only 
approved watertight connectors.

Electrical Specifications

Troubleshooting

Valve will not open.

1.  Ensure main water supply is on.  Ensure 

upstream valves are open.  Ensure flow 
control stem is not closed.

2.  If valve only opens with manual bleed, 

ensure controller is programmed to acti-
vate the proper zone valve. Test controller 
power output and service if necessary. Test 
solenoid power input.
a)  If controller and solenoid power are 

detected, insert a thin flat screwdriver 
into the slotted areas of the solenoid 
bottom and brown solenoid retainer. 
Gently pry to disengage retainer. 
Remove plunger assembly and clean 
debris. 

 

Replace plunger ensuring black surface 
faces outward. Snap retainer into place 
ensuring the larger hole faces outward.  
Persistent problem may be an obstruc-
tion lodged in main pipe.

b)  If power is detected at the control-

ler and not the solenoid, inspect and 
repair damaged lead wires.

Valve will not close.

1.  Ensure controller is not operating the valve 

automatically. Ensure manual internal 
bleed is off by clockwise tightening the 
solenoid adapter. Ensure manual external 
bleed is off by clockwise tightening the 
valve bleed screw.

2.  Turn off water supply and swap solenoid 

from an operational valve; replace solenoid 
if necessary.

3.  Turn off water supply and verify that the 

solenoid adapter o-ring is not damaged; 
replace if necessary.  Check for debris in 
solenoid bowl preventing plunger from 
creating a positive seal.

4.  Check overall system water-pressure 

requirements and ensure that multiple 
zone valves are not operating simultane-
ously.  Disallowing one zone valve to close 
before another opens can reduce the 

English

A

B

C

D

F1

G4 Solenoid

Troubleshooting (cont.)

• 24VAC 50/60Hz (cycles/sec) solenoid
• Inrush current: 0.41A (9.9VA) at 50/60Hz

• Holding current: 0.14A (3.43VA) at 50/60Hz
• Coil resistance 30-39 ohms nominal

Reviews: