88
ESP-LXIVM Series Controllers
C
At the Action Under High Flow screen, press the + and – keys to
set the desired option to occur under High Flow, then press next
D
At the Action Under Low Flow screen, press the + and – keys to
set the desired option to occur under Low Flow, then press next
C
Action Under High Flow
Next
Diagnose & Eliminate
D
Action Under Low Flow
Next
Alarm Only
E
At the Re-enable time screen, press the + and – keys to set the
desired number for hours (from 0 to 23). Press the Arrow keys to nav-
igate between the number setting fields. Set the minutes (from 0
to 59).
E
Re-enable time
Done
Resume irrigation in
After a flow alarm.
23
: 59
HH :MM
Current Flow Reading
Occasionally it may be useful to check the current flow rate in a par-
ticular FloZone and how that compares to previously learned or user
input station flow rates.
Turn the controller dial to Flow Sensor
A
At the FLOW SENSOR screen, press the Down Arrow key to select
Set Current Flow Reading, then press Next.
B
At the View Current Flow screen, press the + and – keys to select
the desired FloZone number. Current and expected flow will
show.
A
FLOW SENSOR
Next
Current Flow Reading
Set Flow Units
Set FloWatch
Set FloManager
Set Flow Rates
B
View Current Flow
Current:
100.0 GPM
110.0 GPM
Expected:
10%
Deviation
Back Next
FloZone
1
B
NOTE: Expected flow is from previously user-entered or learned
station flow rates. The deviation or percentage comparison of
current flow to expected flow will show so you can see how
close each FloZone is to a High Flow or Low Flow condition (see
Setting Up High Flow and Low Flow for more details).