889-1600-04
Model P-1400 Operations Manual Rev Apr 2020 Page
20
of 33
To set the mapping status of the Vital Input when in the Primary Vital Output Mapping Program Mode, press the
CHAN
pushbutton once. The right character will flash indicating the current setting and the sixth bargraph
segment from the left will show the corresponding Vital Input mapping. Use the
(UP) or
(DOWN)
pushbutton to change the setting to the desired configuration. The two combinations of display characters and
bargraph display are shown below.
When in Normal Mode, repeatedly press the
FUNC
pushbutton to enter Program Mode and toggle through the set-
up parameters until the display screen shows the bargraph and two of the seven segment display characters. The
left character will flash indicating the current setting and the four leftmost bargraph segments will show the
corresponding Loop Status Input mapping. Press the
CHAN
pushbutton once. The right character will flash
indicating the current setting and the sixth bargraph segment from the left will show the corresponding Vital Input
mapping. Use the
(UP) or
(DOWN) pushbutton to change the setting to the desired configuration. The two
combinations of display characters and bargraph display are shown below.
5.2.2
AUXILIARY VITAL OUTPUT MAPPING SCREENS
P
ARAMETER
...................Auxiliary Vital Output Mapping.
S
ETTINGS
........................512 selections - any and all combinations of the four Loop
Status Inputs, the Vital Input, and the four Health Status Inputs.
S
ETTING
D
ISPLAYED
......Bargraph indicates Loop Status Inputs, Vital Input, and/or
Health Status Inputs mapped to the Auxiliary Vital Output. In
Loop Status Input mode, the leftmost segment = Loop Status
Input 4, next segment = Loop Status Input 3, next segment =
Loop Status Input 2, next segment = Loop Status Input 1. In
Vital Input mode, the sixth segment from left = Vital Input. In
Health Status Input mode, the rightmost segment = Health
Status Input 1, next segment = Loop Status Input 2, next
segment = Loop Status Input 3, next segment = Loop Status
Input 4.
7
S
EGMENT
D
ISPLAY
......7-segment display will show currently selected setting. The
first character corresponds to the Loop Status Inputs mapped to
the Auxiliary Vital Output, the second character corresponds to
the Vital Input mapped to Auxiliary Vital Output, and the third
character corresponds to the Health Status Inputs mapped to the
Auxiliary Vital Output.
D
EFAULT
S
ETTING
..........000. No Loop Status Inputs mapped to the Auxiliary Vital
Output. Vital Input not mapped to the Auxiliary Vital Output.
No Health Status Inputs mapped to the Auxiliary Vital Output.
E
XAMPLE
........................Loop Status Inputs 1, 2, & 3 mapped to the Auxiliary Vital
Output. Vital Input not mapped to the Auxiliary Vital Output.
Health Status Inputs 1, 2, 3, & 4 mapped to the Auxiliary Vital
Output.
N
OTES
.............................The first and third characters are displayed in Hexadecimal
notation (Base 16).
To set the mapping status of the Loop Status Inputs, repeatedly press the
FUNC
pushbutton to enter Program
Mode and toggle through the set-up parameters until the display screen shows the bargraph and three of the seven
segment display characters. The left character will flash indicating the current setting and the four leftmost
bargraph segments will show the corresponding Loop Status Input mapping. Use the
(UP) or
(DOWN)
pushbutton to change the setting to the desired configuration. The various combinations of display characters and
bargraph display are shown on the next page.
Display Setting
Vital Input Mapping Status
Vital Input not mapped to the Primary Vital Output.
Vital Input mapped to the Primary Vital
Output.
©