the FYA channel and the associated protected channel. The FYA channel follows the permissive of the associated
opposing thru..
DISABLE FLASH RATE- If
NO
(default) is selected flash rate monitoring is active. If
YES
when the FYA is on
for greater than 700 milliseconds, the MMU2 will fail with a Dual Indication failure. Bit 81 of the Type 129
PED YELLOW REMAP- This setting is not editable by the user. It is set using the MMU2 Wizard Configuration.
4.6.2.1.7.7
THRESHOLD SETTINGS
Use the up (▲) or down (▼) pushbutton to
navigate between the settings. Use the
ENTER
pushbutton to toggle
the setting. Press the
ESCAPE
pushbutton to exit.
LED THRESHOLDS – When this feature is enabled the monitor will use more restrictive AC voltage thresholds
for determining the ON and OFF state of field indications. See Section 2.6.4
for more information. The factory
default for this feature is
NO
.
24V-2 TO 12VDC – When this feature is enabled the +24V Monitor II input thresholds will be modified to
m12 VDC. The new voltage threshold will be 11.5 VDC and above, sensed as valid; 10.75 VDC and
below, sensed as invalid. Voltages between these thresholds may be sensed as valid or invalid. See Section 2.6.7
for more information. The factory default for this feature is
NO
.
4.6.2.1.7.8
LOGGING OPTIONS
Use the up (▲) or down (▼) pushbutton to
navigate between the settings. Use the
ENTER
pushbutton to toggle
the setting. Press the
ESCAPE
pushbutton to exit.
LOG FIELD CHANGES – When this feature is enabled the monitor will make entries in the Signal Sequence log
only when an input has changed state. Otherwise, the Signal Sequence log records an entry every 33 milliseconds.
See Section 2.7.7.1 for more information. The factory default for this feature is
NO
.
LOG LOCAL FLASH EVENTS – When this feature is enabled the monitor will record Local Flash events in the
Prior Faults log. See Section 2.7.7.2 for more information. The factory default for this feature is
YES
.
LOG CVM EVENTS – When this feature is enabled the monitor will record CVM events in the Prior Faults log.
See Section 2.7.7.3 for more information. The factory default for this feature is
YES
.
4.6.2.1.7.9
OTHERS / MISCELLANEOUS LOCATION SETTINGS
Use the up (▲) or down (▼) pushbutton to
navigate between the settings. Use the
ENTER
pushbutton to toggle
the setting. Press the
ESCAPE
pushbutton to exit.
DISABLE LOCAL FLASH – When this feature is enabled the monitor will ignore the Local Flash input. The
LOC FLASH
indicator will show this function as disabled (50 milliseconds on, once every two seconds) when
this feature is enabled. This feature can be useful in scenarios where you want to temporarily disable Local Flash.
See Section 2.6.8 for more information. The factory default for this feature is
NO
.
MODIFIED CVM LATCH – When this feature is enabled and the CVM Latch Enable jumper is installed on the
programming card, the CVM input will not latch a CVM failure until the CVM input has been valid for more than
175 milliseconds. See Section 2.6.6 for more information. The factory default for this feature is
NO
.
EXTERNAL WATCHDOG ENABLE – When this feature is enabled the monitor will verify the status of an
optional external watchdog output from a Controller Unit or other external cabinet device. See Section 2.5.13 for
more information. The factory default for this feature is
NO
.
TYPE 16 ONLY – When this feature is enabled the monitor will always operate in the Type 16 mode. See Section
2.4.4 for more information. The factory default for this feature is
NO
.
DISABLE BUZZER – When this feature is enabled the monitor will not use the buzzer to annunciate a pending
configuration change. This feature can be useful in the lab environment where many changes are being made to
the monitor for testing purposes. It is not recommended that this feature be enabled for any monitor in the field.
The factory default for this feature is
NO
.
4.6.2.1.8
FACTORY SETTINGS
This display is view only. Press the
ESCAPE
pushbutton to exit.
FLASHING GREENS – When this feature is enabled the monitor will modify its Red Fail and Dual Indication
timings to deal with the fast flashing Green indications used in Canada. Only monitors used in Canada should have
this factory option enabled. See Section 2.6.9 for more information.
ECONOLITE FRAMES – When this feature is enabled the monitor will respond to special SDLC frames requested
by Econolite controllers.