6
The
LEDs local to the panel
are as follows:
Alarm
Internal/ Colour
Description
External
Or Alarm
I
Red
on if any sensor currently has an over range alarm
Lo Alarm
I
Red
on if any sensor currently has a low alarm
Hi Alarm
I
Red
on if any sensor currently has a high alarm
DC fail
I
Amber
on if battery is low
AC fail
I
Amber
on if mains has failed
Sensor fail
I
Amber
on if any sensor has failed
CAN fail
I
Amber
on if any addressable sensor has stopped communicating
Modbus fail
I
Amber
on if the Modbus master has stopped communicating
System Inhibit
I
Amber
on if the system is not checking alarms
Sensor Inhibit X
Amber
on if any sensor has been inhibited
MPU fail
I
Amber
on if the processor has had a watchdog reset
Power
I
Green
on if power applied
Fault
X
on if a fault exists
Alarm
X
on if alarm exists
(I = view internal X = view external)
If the fault or alarm LED is flashing, this indicates a new event and when accepted by
pressing the up (1) button it remains on (not flashing).