Set Modbus Baud
This menu allows you to change the Baud rate used by the Modbus (default is 9600). The options
are 19200, 9600, 4800 bits per second and these are altered using the UP and DOWN buttons,
Pressing SELECT will exit from this menu.
35]
Set Power Alarms
The panel detects both mains power and battery/DC power. When only one power source is in
use it is convenient to disable the loss detection of the other source so that the panel is not in
continuous fault. This menu allows you to inhibit the battery alarm first and by pressing SELECT
then the mains alarm. The + and – buttons toggle whether or not each alarm is inhibited, this is
displayed on the LCD. Pressing SELECT will exit this menu.
36]
Set Energised Relays
This menu allows relays to be set as normally energised (=1) or de-energised (=0).
4321FOHL represents the 8 on board relays.
L = Low alarm
H = High alarm
O = Over range alarm
F = Fault relay
1,2,3,4, = the 4 option relays used in groups 1 to 4
Using + and - buttons, the small cursor moves along a pattern of ones and zeros which represent
the normally de-energised or energised setting and this can be changed using the UP and DOWN
buttons.
Press SELECT to exit this menu.