2.0 INSTALLATION

The RP, GP and XP Series Fans can be mounted indoors or outdoors. (It 
is suggested that EPA and radon mitigation standards recommendations 
be followed in choosing the fan location.) The GP fans have an integrated 
mounting bracket; RP and XP Series Fans may be mounted directly on 
the system piping or fastened to a supporting structure by means of an 
optional mounting bracket.
The ducting from the fan to the outside of the building has a strong effect 
on noise and fan energy use. Use the shortest, straightest duct routing 
possible for best performance, and avoid installing the fan with smaller 
ducts than recommended. Insulation around the ducts can reduce energy 
loss and inhibit mold growth. Fans installed with existing ducts may not 
achieve their rated airflow.

2.1 MOUNTING

Mount the RP, GP and XP Series Fan vertically with outlet up. Insure the unit is 
plumb and level. When mounting directly on the system piping assure that the fan 
does not contact any building surface to avoid vibration noise.

2.2 MOUNTING BRACKET (optional)

The RP and XP Series Fans may be optionally secured with the RadonAway P/N 
25007 mounting bracket. Foam or rubber grommets may also be used between 
the bracket and mounting surface for vibration isolation.

2.3  SYSTEM PIPING

Complete piping run, using flexible couplings as a means of disconnect for 
servicing the unit and for vibration isolation. As the fan is typically outside of the 
building thermal boundary and is venting to the outside, installation of insulation 
around the fan is not required.

2.4 ELECTRICAL CONNECTION

Connect wiring with wire nuts provided, observing proper connections (See Section 
1.9). Note that the fan is not intended for connection to rigid metal conduit.

2.5 VENT MUFFLER (optional)

Install the muffler assembly in the selected location in the outlet ducting.  Solvent 
weld all connections. The muffler is normally installed at the end of the vent pipe.

TYPICAL OUTDOOR INSTALLATION

TYPICAL INDOOR INSTALLATION

2.6  OPERATION CHECKS & ANNUAL SYSTEM MAINTENANCE

 

______   Verify all connections are tight and leak-free.

 

______   Ensure the RP, GP and XP Series Fan and all ducting are secure and vibration-free.

 

______   Verify system vacuum pressure with manometer. Insure vacuum pressure is within normal    

 

 

  operating range and less than the maximum recommended operating pressure.

 

 

 

(Based on sea-level operation, at higher altitudes reduce by about 4% per 1000 feet)

 

 

 

(Further reduce Maximum Operating Pressure by 10% for High Temperature environments.)

   See Product Specifications. If this is exceeded, increase the number of suction points.

 
 

______   Verify Radon levels by testing to EPA Protocol and applicable testing standards.

Summary of Contents for RP140

Page 1: ...IN095 Rev B 0718 1 3 Saber Way Ward Hill MA 01835 radonaway com RP GP XP Pro Series Installation Instructions...

Page 2: ...m this non operational storage 6 WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING a Use this unit only in the manner intended by the manufacturer If you hav...

Page 3: ...stallation For bathroom and general ventilation applications at least 8 feet of insulated flexible duct shall be installed between the exhaust or supply grille s and the fan s RP GP and XP Series Fans...

Page 4: ...o notify the occupants of a fan system malfunction A System Label provided with Manometer P N 50017 with instructions for contacting the installing contractor for service and identifying the necessity...

Page 5: ...et and mounting surface for vibration isolation 2 3 SYSTEM PIPING Complete piping run using flexible couplings as a means of disconnect for servicing the unit and for vibration isolation As the fan is...

Page 6: ...0 251 209 157 117 70 26 RP265 375 330 282 238 204 170 140 108 70 RP380 531 490 415 340 268 200 139 84 41 Model Size Weight Inlet Outlet L 2 RP140 8 5 H x 9 7 Dia 5 5 lbs 4 5 OD 4 0 PVC Sched 40 size c...

Page 7: ...1000 ft of altitude GP Series Product Specifications Model Recommended Duct PVC Pipe Mounting Thermal Cutout Insulation Class RP140 3 or 4 Schedule 20 40 PVC Mount on the duct pipe or with optional m...

Page 8: ...ranty Proof of purchase must be supplied upon request for service under this Warranty 5 YEAR EXTENDED WARRANTY WITH PROFESSIONAL INSTALLATION RadonAway will extend the Warranty Term of the fan to 60 m...

Reviews: