Under certain circumstances, a flexible pipe coupling, RadonAway
p/n 79019-1, may ease installation. This may be particularly
true of gable side installations where the system piping runs
perpendicular to the floor joists. Install the pipe coupling as
shown in Figure 6, making certain to avoid sharp bends or kinks
in the piping. (TIP: You may connect the pipe coupling to the
GP500 before installing the unit through the band joist.)
2.3 MUFFLER INSTALLATION (Optional)
Install the vent muffler assembly in the selected location in the
outlet ducting. Solvent weld all connections. The muffler is
normally installed at the end of the vent pipe.
2.4 OPERATION CHECKS & ANNUAL SYSTEM MAINTENANCE
____ Verify all connections are tight and leak-free.
____ Ensure the GP500 and all ducting is secure and vibration-free.
____ Verify system vacuum pressure with Manometer or other pressure gauge. Ensure vacuum pressure is within
normal operating range and less than 3.8” WC (based on sea-level operation, at higher altitudes reduce by
about 4% per 1000 Feet). If this is exceeded, increase the number of suction points.
____ Verify Radon levels by testing to EPA Protocol and applicable testing standards.
PRODUCT SPECIFICATIONS
The following chart shows fan performance for the GP500:
Power: 85-153 watts (varies with actual load conditions) @ 115 VAC
Inlet/Outlet:
3” PVC
Mounting:
Brackets for vertical mount on bandjoist or sidewall. (16” Mounting Centers)
Outdoor installations: GP500 mounts flush to wall projecting only 4” with inlet duct passing
through the sidewall or band joist. Power cord is on the inside, simplifying connection.
Weight: 20 lbs.
Recommended ducting: 3” Schedule 20/40 PVC Pipe or attractive thin walled 3” O.D. PVC
Storage Temperature Range: 32-100 degrees F
Thermally protected
Size:
17” x 12” x 4” (plus 7” inlet duct)