background image

Page 5 of 22

IN052   Rev. K   0613

Mid-Range Flow Rate Test:

1. 

Attach garden hose to the drain connection on the base of the Well Pressure Tank.

2. 

Open the drain valve and run water for 15 minutes.

3. 

After 15 minutes, check the pressure gauge on the well system. Adjust the drain valve (open or 

close) as needed to maintain the required running system pressure (constant pressure on gauge) 

with the well pump running continuously.

4. 

Run for 5 minutes while ensuring that the pressure is not fluctuating.

5. 

Run water from the hose into a five gallon bucket. Using a stop watch, time how many seconds it 

takes to fill the bucket (Z sec.).

6. 

Determine the GPM by dividing 60 seconds by the number of seconds it took to fill the bucket (Z 

sec.).   Multiply the answer by 5 gallons. This gives you the GPM.
 

 

 

 

 

GPM = ( 60 / Z ) x 5

7. 

Repeat steps 5 and 6 and average the 2 numbers. The answer is the well pump output in gallons per 

minute. It is recommended that this number be indelibly recorded in an obvious location, together 

with the date of test, as it will be required when setting the AIRaider

 EZ

95

 System and may be re-

quired for future troubleshooting of the well pump system or the AIRaider

 EZ

95

 System.

Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage!

1.3.   Full Water Test

A full Water Sample Analysis must be performed to determine the quality of the water that requires treat-

ment. In many water supplies, contaminants other than radon are present. The AIRaider

 EZ

95

 System 

is only effective for the removal of radon and some other VOCs. The Aeration Process employed by the 

AIRaider

 EZ

95

 System and other radon removal systems can worsen problems due to iron or manganese 

contaminants in the water supply. For optimal removal of radon or other VOCs, other contaminants such as 

sediment, iron, or manganese must be removed before the water supply enters the AIRaider

™ 

EZ

95

1.4.   Unpacking and Locating System Components

 

1.4.1.  Unpack All System Components

 

Remove all packing material and discard appropriately away from the work area.

 

1.4.2.  Locate All Components

 

Check to ensure all components are intact and included in shipment.

 

Included Component List (may vary with order)

• 

 Tank Assembly

• 

 Pump (Installed Inside Tank Assembly)

• 

 Diffuser Assembly (Installed Inside Tank Assembly)

• 

 Bypass Valve (Sold Separately)

• 

 Bladder Tank (Minimum 5 gallon. Sold Separately)

• 

 Manual

Household water use must be discontinued during the following flow rate test.

PRE-INSTALLATION

1

Summary of Contents for AIRaider EZ95

Page 1: ...AIRaider EZ95 Installation Instruction Manual RadonAway 3 Saber Way Ward Hill MA 01835 radonaway com IN052 Rev K 0613...

Page 2: ...Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING 6 ALARM SCHEMATIC 7 BLOWER BRUSH REPLACEMENT 8 EQUIPMENT SPECIFICATION LIMITED WARRANTY...

Page 3: ...afety 2 Installation site requirements 3 Inspection of System components 4 Qualified Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Matters Safety is the most import...

Page 4: ...he system output the AIRaider EZ95 may run dry which will cause the pump installed integrally within the AIRaider EZ95 System to automatically shutdown To prevent outflow interruptions it is strongly...

Page 5: ...tem or the AIRaider EZ95 System Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage 1 3 Full Water Test A full Water Sample Analysis must be...

Page 6: ...5 System in accordance with the installation instructions Check your Local and State Code and Licensing requirements Failure to follow the instructions may lead to poor system performance and or possi...

Page 7: ...Raider EZ95 System are listed below Read all components of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical...

Page 8: ...ing necessary this is typically in proximity to the well tank 2 Electrical Hook up Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power supply 3 Exhaust Line Venting The location...

Page 9: ...r level Pump float 3 Cable length tether to float normally open prevents pump dry running Vent On off float Float switch hose clamp Check valve behind pressure regulator Vent pipe hose clamps Push but...

Page 10: ...gned for use with a pressure tank The pressure tank bladder pressure should be set per the tank manufacturers recom mendations for a pressure switch setting of 37 psi 9 An outlet pipe must be installe...

Page 11: ...N C Blower Neon Lamp Push Button Thermostat Over Ride A B 1 2 C D E Blower Enclosure Electrical Enclosure Wiring NEZ SRT B G W B W W B B B B W W B B B R R R R W W W R RRG RRG B B W B W B B B B B B B B...

Page 12: ...tion 4 Ensure that the red lead provided for an optional auxiliary fan remains insulated if not used The red lead is the live feed from the Aeration System to the Fan Warning Do Not connect any of the...

Page 13: ...st be wired to the system electrical box connections as shown in the Electrical Schematic Figure 8 This will ensure that the fan operates only when required by the system The red lead is the live feed...

Page 14: ...ystem Start Up 1 Remove cover and lid and pour cup of chlorine into the AIRaider tank This will disinfect the system Secure the lid with the screws and washers provided 2 Check that all plumbing and e...

Page 15: ...given in Table 1 for the measured well pump output This is done by temporarily attaching a hose to the house connection of the bypass valve and adjusting the flow control valve to provide the correct...

Page 16: ...should be followed to maintain the AIRaider Check and or clean the blower air intake filter Check and or clean any filters or strainer installed on the inlet line to the AIRaider In installations with...

Page 17: ...f necessary Clean if necessary tank and diffusers of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the tank Check all control panel connections and electrical componen...

Page 18: ...not illuminated Check power switch in on position circuit breaker at panel in on position Check pump float switch for proper operation Check that the pump priming orifice rear left behind pump is not...

Page 19: ...Page 19 of 22 IN052 Rev K 0613 6 ALARM SCHEMATIC ALARM SCHEMATIC 1 2 3 4 5 6...

Page 20: ...ve the brush holder assembly from the motor 6 Insert the new brush holder assembly making certain that brass prongs engage the electrical socket and then replace the retaining screw 7 Repeat steps 4 6...

Page 21: ...0 VAC Buna N Seal Brass Valve Body NPT System Voltage 115V Electric Supply 20 Amp 115VAC Dedicated Circuit Recommended Flow Up to 7 GPM Radon Reduction Up to 95 Water Inlet Outlet Connections Sharkbit...

Page 22: ...AR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALID In order to ob...

Reviews: