Radionics D9024 Installation Instructions Manual Download Page 6

1997 Radionics                All rights reserved

The Radionics logo is a registered trademark of Radionics,

    1800 Abbott Street, Salinas, CA  93901, USA

74-07649-000-B        01/97
D9024/D10024 Installation

Page 6 of 17

Polling circuits can be connected to the FACP as either a Class “A” or a Class “B” circuit.  “T” tapping

is acceptable in Class “B” circuits.  For specific Class “A” and “B” circuit installation requirements,

see NFPA 72.

B.2  Peripheral Circuits

The RS 485 Bus Circuit provides an optically isolated data interface between the Control Module and

Command Centers and Annunciators, networked panels, serial peripherals, and computer graphics

systems.  A shielded twisted pair wiring circuit connects to the D9051 RS 485 Bus Module.  The

three ports on the left side of the control module are mounting points, depending on the application,

for the D9051 Modules.
The D9052 RS 232 Module provides an isolated interface between the Control Module and dial-up or

dedicated modems.  Modems allow communication over telephone lines between networked panels,

system controllers, computer graphics packages, and other serial peripherals when the circuit

distance is greater than 3,250 feet.

RS 485 Peripheral Circuit Length

Wire Gauge

Up to 4,920 ft.

18

Table 2:  RS 485 Peripheral Circuit Length/wire Gauge

B.3  Notification Appliance (Indicating Device) and Output Circuit Connections

The D9024 and D10024 each has four power-limited and supervised Class “B,” Style “W” indicating

circuits. The terminal blocks for these circuits are at the lower edge of the Control Module.  (See

Figure 3

.)  Each indicating circuit must be terminated with a 2k End Of Line (EOL) resistor (Part No.

25899C, manufactured by Detection Systems).  Four resistors for the indicating circuits are included

in the Literature Pack.  Each circuit has a maximum rating of one Amp.

See Compatible Device List: 

Devices Compatible with the D10024 Analog Fire Alarm Control Panel

,

Part No. 73-07674-000-A, for devices acceptable for use in the indicating circuit.

The D9024 and D10024 each has terminals for a power-limited auxiliary 24 V circuit at the lower left

of the Control Module.  This circuit is rated at one Amp maximum. If the system requires more than

four circuits use the D327 Indicating Circuit Module to add circuits as required.
The total current of the five circuits (four “SOUNDER OUTPUTS” PLUS “24V AUX.”) must not

exceed two Amps.
The D9024 and D10024 each has two programmable relay contacts rated 24 V DC, 1 Amp.

Caution: Do not connect any wiring that is not power-limited to the relay contacts.

AUX RELAYS

RELAY 2

RELAY 1

24V. AUX

O

V.

24

V.

SOUNDER
OUTPUTS

A-

A+

B-

B+

C-

C+

D-

D+

N/C

N/O

COM

N/C

N/O

COM

Figure 3: Output Connection Points on the D9024 and D10024M Control Module

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for D9024

Page 1: ...o provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio frequency energy and if not installed in accordance with t...

Page 2: ...stallation 8 C 2 b D9067 Module Connection to the Control Module 9 C 2 c D9067 Module Connection to Class B Style 4 Circuit 9 C 2 d D9067 Module Connection to Class A Style 6 Circuit 10 C 2 e Shielded...

Page 3: ...Circuit Module Installation 8 Figure 7 Stacked Modules 9 Figure 8 D9067 Class B Style 4 Connection 9 Figure 9 D9067 Class A Style 6 Connection 10 Figure 10 D10024 Control Module Configuration 11 Figur...

Page 4: ...ircuits use types FPL FPL R or FPLP cable as applicable per NEC Article 760 A 1 Semi flush Mounting 1 Prepare an opening in the wall 20 x 20 x 5 1 2 2 Remove the knockouts asnecessary forwiring condui...

Page 5: ...nts other than attention to the wire gauge Under extremely noisy conditions twisted pair wire is recommended to reduce interference If EMI is a problem use shielded cable being careful to ground the d...

Page 6: ...ge B 3 Notification Appliance Indicating Device and Output Circuit Connections The D9024 and D10024 each has four power limited and supervised Class B Style W indicating circuits The terminal blocks f...

Page 7: ...ogrammed into the panel and are stored in the Central Processing Unit CPU to each analog device These levels can be altered through the front panel or PC programming Each device is programmed for Alar...

Page 8: ...as shown in Figure 6 COM 24V AUX 0V COM N C 24V N O N C N O AUX RELAYS RELAY 1 RELAY 2 OUT IN LOOP E 5 OUTPUTS SOUNDER 1 EARTH 2 DC DC E LOOP 4 E 3 LOOP E LOOP 2 E LOOP 1 D10024 Control Module 8 Wire...

Page 9: ...e Ribbon Socket 8 wire Ribbon Socket Figure 7 Stacked Modules C 2 c D9067 Module Connection to Class B Style 4 Circuit Connect the Data Power Positive wire of the polling circuit to the terminal of th...

Page 10: ...on Return Data Power Positive Out Data Power Common Out Figure 9 D9067 Class A Style 6 Connection C 3 D9051 RS 485 Bus Module The D9051 module is an RS 485 Network Expander It provides an isolated Cla...

Page 11: ...above Ports B C and D See Figure 10 COM 24V AUX 0V COM N C 24V N O N C N O AUXRELAYS RELAY1 RELAY2 LOOP E 5 OUTPUTS SOUNDER 1 EARTH 2 DC DC E LOOP 4 E 3 LOOP E LOOP 2 E LOOP 1 D10024 Control Module 8...

Page 12: ...e top of the D9051 Module Connect the A wire to the A terminal next to it If Shielded cable is used connect the drain wire s to the E terminal of the terminal block at the top of the Control Module Bo...

Page 13: ...hem in the same conduit and keep them apart inside the enclosure Connect the ground wire to the ground input middle terminal on 3 Amp fuse holder See Figure 13 The 120V neutral and line wires connect...

Page 14: ...300 A 300 mA x Qty 300 A 300 mA x Qty D327 320 A 320mA x Qty 320 A 320 mA x Qty 320 A 320 mA x Qty D329 280 A 280mA x Qty 280 A 280 mA x Qty 280 A 280 mA x Qty Other devices connected to the system n...

Page 15: ...No one to the negative terminal of battery N o two Connect the red wire lead from terminal 6 on the Power Supply to the positive terminal of battery No two Connect the black wire lead from terminal 7...

Page 16: ...LARM LED ALARM SILENCED LED AC POWER LED TROUBLE SILENCE KEY ALARM SILENCE KEY FIRE DRILL KEY 0 1 2 4 3 5 7 8 9 CHANGE System Trouble A N SHIFT 1 3 Alarm B O C P LED DISPLAY 7 Earth Fault 5 4 6 Troubl...

Page 17: ...el s internal buzzer will sound and the alphanumeric display will provide detailed information E 3 Alarm Conditions The red Alarm LED at the left of the indicator display flashes to indicate the syste...

Reviews: