background image

7

Radionics, Inc.
74-07113-000-B  4/94

Battery Voltage

Scale

Volts

Light

13.75

1

Minimum Battery

13.25

2

12.75

3

Read Battery

12.25

4

11.75

5

11.25

6

10.75

7

10.25

8

Voltage

Low battery flashes
lights 5, 6, 7, 8.

Voltage after
1 Minute

Summary of Contents for D2112

Page 1: ...gth is 3 so if you have not changed the default entries press 654 Lights on the keypad indicate the functions that are available Now that you re in When you select a function the light next to the key...

Page 2: ...the low battery condition appears in the Check Trouble Mode When the Battery Test is initiated by the user initiating Test System a Low Battery report or a Missing Battery report will be sent if progr...

Page 3: ...nter the Relays function 2 Press and hold 1 to activate relay 1 light 1 will be on while you hold the key 3 Press and hold 2 to activate relay 2 light 2 will be on while you hold the key 4 Press CLEAR...

Page 4: ...vate and the current consumption displays 4 Hold the Current Consumption scale next to your keypad Verify that the current consumption is less than 860mA 5 Press CLEAR 6 Reconnect the battery To displ...

Page 5: ...Current Consumption Scale mA Light Maximum Fire 860 1 732 2 605 3 477 4 Maximum Normal 350 5 222 6 95 7 8 Alarm Load Supervisory Load When a test indicates an overload condition the bar graph flashes...

Page 6: ...d gives an acknowledge tone after 1 minute 4 Hold the Battery Voltage scale up next to your keypad Verify that the battery does not drop below 13 25 volts within the minute 5 Press CLEAR To Read Batte...

Page 7: ...7 Battery Voltage Scale Volts Light 13 75 1 Minimum Battery 13 25 2 12 75 3 Read Battery 12 25 4 11 75 5 11 25 6 10 75 7 10 25 8 Voltage Low battery flashes lights 5 6 7 8 Voltage after 1 Minute...

Page 8: ...iagnostics Mode 2 Press 4 If light 5 is lit a system trouble exists To find out what the trouble is 3 Press and hold key 5 The lights indicate the specific type of trouble Low or Missing Battery 1 Sta...

Reviews: