Power Supply Status 

(Cont'd)

To enter the Power Supply Status mode,

1. Press ( 7 ).

Light 7 winks to let you know that you’re in
the Power Supply Status function.

…To display Fire Alarm Load

2. Disconnect the battery.

3. Press ( 1 ).

The bell and external relays activate, and
the current consumption displays.

4. Hold the Current Consumption scale next to

your keypad. Verify that the current
consumption is less than 860mA.

5. Press ( CLEAR ).

6. Reconnect the battery.

…To display Normal Supervisory Load

2. Disconnect the battery.

3. Press ( 5 ).

The current consumption displays.

4. Hold the Current Consumption scale next to

your keypad and verify that the current
consumption is less than 350mA.

5. Press ( CLEAR ).

6. Reconnect the battery.

7

Radionics, 1 Park Gate Close, Bredbury,
Stockport, Cheshire, SK6 2SZ, England
Technical Support: (061) 494-0851

Summary of Contents for D2112

Page 1: ...gth is 3 so if you have not changed the default entries press 654 Lights on the keypad indicate the functions that are available Now that you re in When you select a function the light next to the key...

Page 2: ...the low battery condition appears in the Check Trouble Mode When the Battery Test is initiated by the user initiating Test System a Low Battery report or a Missing Battery report will be sent if progr...

Page 3: ...nter the Relays function 2 Press and hold 1 to activate relay 1 light 1 will be on while you hold the key 3 Press and hold 2 to activate relay 2 light 2 will be on while you hold the key 4 Press CLEAR...

Page 4: ...vate and the current consumption displays 4 Hold the Current Consumption scale next to your keypad Verify that the current consumption is less than 860mA 5 Press CLEAR 6 Reconnect the battery To displ...

Page 5: ...Current Consumption Scale mA Light Maximum Fire 860 1 732 2 605 3 477 4 Maximum Normal 350 5 222 6 95 7 8 Alarm Load Supervisory Load When a test indicates an overload condition the bar graph flashes...

Page 6: ...d gives an acknowledge tone after 1 minute 4 Hold the Battery Voltage scale up next to your keypad Verify that the battery does not drop below 13 25 volts within the minute 5 Press CLEAR To Read Batte...

Page 7: ...7 Battery Voltage Scale Volts Light 13 75 1 Minimum Battery 13 25 2 12 75 3 Read Battery 12 25 4 11 75 5 11 25 6 10 75 7 10 25 8 Voltage Low battery flashes lights 5 6 7 8 Voltage after 1 Minute...

Page 8: ...iagnostics Mode 2 Press 4 If light 5 is lit a system trouble exists To find out what the trouble is 3 Press and hold key 5 The lights indicate the specific type of trouble Low or Missing Battery 1 Sta...