SERVICING AND MAINTENANCE INSTRUCTIONS
_
GAS DATA TABLE
Natural Gas
G 20
Liquid Butane Gas
G 30
Liquid Propane Gas
G 31
Lower Wobbe index (15°C; 1013 mbar) MJ/Nm
3
45.67 80.58
70.69
Rated feed pressure
mbar
20
30
37
Main burner: 13 Jets - Ø jet
mm
1.25
0.77
0.77
Consumption (15°C; 1013 mbar) m
3
/h 2.83
-
-
Consumption (15°C; 1013 mbar)
kg/h
-
2.11
2.08
GAS PRESSURE SETTING
NATURAL GAS G20
G.P.L. G 30 / G 31
min. max. max min.
6.5 11.4 30 6
SLOW IGNITION ADJUSTMENT
This is a slow ignition regulator whose trimmer is factory set to the
minimum.
For adjustment proceed as follows:
if turned clockwise the gas pressure at the burner increases on ignition
while turning counter-clockwise decreases the gas pressure.
ANTI CYCLING DEVICE
This allows the various ignitions to be delayed once the boiler has
reached the optimum temperature.
The time range goes from 0 up to 7.5 minutes.
Fig. 1
CONDENSING WALL-HUNG BOILER – TG05A062.A0505