SERVICING AND MAINTENANCE INSTRUCTIONS
_
PARAMETERS TABLE
PARAMETER
NUMBER
TYPE OF OPERATION
PARAMETER
VALUE
FUNCTION
0
BOILER TYPE SELECTION
00
01
WALL MOUNTED OR FLOOR STANDING
OIL FLOOR STANDING UNIT
1
BOILER TYPE SELECTION
00
01
02
INSTANTANEOUS
WITH STORAGE CYLINDER
WITH STORAGE CYLINDER-COMFORT (+
7°C)
2
GAS TYPE SELECTION
00
01
NATURAL GAS
L.P.G.
3
HEATING TEMPERATURE
SETTING
00
01
STANDARD: from 30 to 80°C
REDUCED : from 25 to 40°C
4
PUMP SETTING IN HEATING
MODE
00
01
STANDARD (PUMP OVERRUN 3”)
PERMANENT (PUMP ON ALL THE TIME)
5
WATER-HAMMER PREVENTION
SETTING
00
01
EXCLUDED
ACTIVE (2” STANDBY)
6
SHORT CYCLING FUNCTION -
HEATING CIRCUIT
(FACTORY CALIBRATED AT 180” -
PARAMETER VALUE “36” )
00 - 90
EXPRESSED IN STEPS OF 5 SEC.
Ex. 90 x 5 = 450“ (7.5 MIN.)
7
PUMP OVERRUN - HEATING
CIRCUIT
(FACTORY CALIBRATED AT 180”-
PARAMETER VALUE “36” )
00 - 90
EXPRESSED IN STEPS OF 5 SEC.
Ex. 90 X 5 = 450“ (7.5 MIN.)
8
PUMP OVERRUN DOM.
HOT WATER CIRCUIT
(FACTORY CALIBRATED AT 90”)
00 - 90
EXPRESSED IN STEPS OF 5 SEC.
Ex. 90 X 5 = 450“ (7.5 MIN.)
9
MIN. GAS MODULATION SETTING
0 – 50%
FACTORY CALIBRATED (Mechanical minimum)
10
MINIMUM HEATING OUTPUT
SETTING
0 – 50%
FACTORY CALIBRATED
11
MAXIMUM GAS PRESSURE
SETTING - MAXIMUM HEATING
OUTPUT SETTING
MAX GAS - 99
9
Parameter cancelled starting from June 2003
CONDENSING WALL-HUNG BOILER – TG05A062.A0505
24