1.1.20. VENTING
WARNING
In order to ensure proper operation and
efficiency of the device you have to connect the
boiler fume exhaust fitting to the exhaust and fresh
air adapters (loosely supplied in water heaters). It is
recommended to install discharge systems approved
by Radiant.
WARNING
All termination kits must be located and
installed in accordance with local building code and
CSA B149.1 Natural Gas and Propane Installation
Code.
WARNING
For condensate collection please follow
the local codes.
› All exhaust runs shall be sloped such that any
condensate would move towards the combustion
chamber so that it can be collected and drained
via the internal condensate trap of the appliance
(Refer to section 1.1.20).
› All combustion air intake runs where possible
should be sloped in a manner to avoid rain
water, dust or foreign objects from entering the
appliance (Refer to section 1.1.20).
› In case of horizontal polypropylene co-axial
system installation, properly orientate the
horizontal co-axial terminal in relation to the
slopes inside the exhaust pipe and to protect
the combustion air pipe from adverse weather
conditions (Refer to section 1.1.20, sub-section
III (
a
)
and figure 20).
This appliance is certified to be installed using
polypropylene, PVC and CPVC. For Canada use
System 636 polypropylene, PVC and CPVC Type
BH Gas Venting Systems certified to ULC S636.
Types of venting configurations for this appliance
are, co-axial vent (pipe with in a pipe), co-linear
vent (separate pipes for exhaust and combustion
air), and single exhaust vent (uses room air for
combustion).
INSTALLATION
Summary of Contents for R1K 34
Page 6: ......
Page 62: ......
Page 65: ...65 R1K 34 B RAD ING Manuale 1512 2_CSA_TTS 3 USE USER...
Page 66: ...66 R1K 34 B RAD ING Manuale 1512 2_CSA_TTS 3 USE USER...
Page 67: ...67 R1K 34 B RAD ING Manuale 1512 2_CSA_TTS 3 USE USER...
Page 68: ...68 R1K 34 B RAD ING Manuale 1512 2_CSA_TTS 3 USE USER...
Page 79: ......