2. INSTALLATION

INST

ALLER

OPEN-THERM PROTOCOL CONFIGURATION

Use the parameter “OT Protocol version” (see fig.2) 
to configure the iModule based on the version of 
the Open-Therm Protocol used by the boiler:

 › 0 = for boilers with electronic printed circuit 

board NORDGAS;

 › 1 = for boilers with electronic printed circuit 

board HONEYWELL;

 › 2 = non applicable.

CONFIGURATION OF STANDARD/DST TIME

You can switch from standard time to daylight 
saving time (and vice versa), using the parameter 
"DST change" (see figure 2) and modify the time of 
the iModule by one hour, according to the following 
convention:

 › 0 = no change to current iModule time;

 › 1 = add one hour to current iModule time;

 › 255 = remove one hour from current iModule 

time.

TIME ZONE CONFIGURATION

You can manage all of the time zones from -12 
hours to +14 hours, in relation to UTC coordinated 
universal time, with a resolution of half an hour. 

The time zone of the iModule is set using the 
parameter "Time Zone" (see fig.2), within its his 
range [104÷156], according to the following rule:

 · value of parameter “Time Zone” = 128 + 

difference of iModule time in relation to UTC 
time, multiplied by 2.

Examples of Time Zones:

UTC Time (Time Zone 0) = set “Time Zone” = 128;

Western Europe Time (Time one 1) = set "Time 
Zone" = 130;

India Time (Time Zone +5.5) = set “Time Zone” = 
139;

Examples by City:

Paris/Rome = UTC Time + 1 = set “Time Zone” = 
130;

London = UTC Time = set “Time Zone” = 128;

Moscow = UTC Time + 3 = set “Time Zone” = 134;

Kiev = UTC Time +2 = set “Time Zone” = 132;

Tehran = UTC Time +3.5 = set “Time Zone” = 135.

OPEN-THERM (OT) CONFIGURATION OR ROOM 
THERMOSTAT (RT)

For iModule systems connected to Open-Therm 
boilers (configuration–OT), set the parameter 
“Connection Type (OT/RT)” = 0;

For iModule systems connected to Room 
Thermostat boilers (configuration–RT), set the 
parameter “Connection Type (OT/RT)” = 1;

Summary of Contents for iMODULE

Page 1: ...iMODULE RAD ING Manuale 1507 1 User s manual iMODULE Remote Control via Wi Fi or GSM...

Page 2: ...NSTALLER REGISTRATION 4 1 0 2 REGISTERING A NEW USER 4 1 0 3 HOW TO CONFIGURE THE PARAMETERS OF THE NEW UNIT 5 1 0 4 WIRING 7 1 0 5 CONFIGURATION OF IMODULE GSM VERSION 9 1 0 6 CONFIGURATION OF IMODUL...

Page 3: ...ed by qualified personnel only who has technical expertise in the field required to installation and maintenanceofthepartsoftheheatingandDHWproduction systems for civil and industrial buildings as pro...

Page 4: ...0 2 REGISTERING A NEW USER Open the page http app imodule it admin Enter the installer login credentials and click on Login The list of registered users if any will be displayed To add a new User clic...

Page 5: ...lazione_iMODULE_v 1502_EN 1 Installazione_iMODULE_v 1502_EN 2 INSTALLATION INSTALLER 1 0 3 HOW TO CONFIGURE THE PARAMETERS OF THE NEW UNIT To configure the parameters of the new unit click on the adju...

Page 6: ...age all of the time zones from 12 hours to 14 hours in relation to UTC coordinated universal time with a resolution of half an hour The time zone of the iModule is set using the parameter Time Zone se...

Page 7: ...onnections see fig 3 Open Therm connection between iModule and Local Controller 2 wires Connection between the iModule and the Boiler 2 wires via Open Therm or Room Thermostat Relay iModule connection...

Page 8: ...8 iMODULE RAD ING Manuale 1507 1 1 Installazione_iMODULE_v 1502_EN 2 INSTALLATION INSTALLER WIRING DIAGRAM OF OPENTHERM BOILER WIRING DIAGRAM OF ROOM THERMOSTAT BOILER fig 4 fig 5...

Page 9: ...e case of telephone provider TRE To insert the SIM card into the iModule see fig 6 Send an SMS to the telephone number associated to the SIM card inserted in the iModule with the following format APN...

Page 10: ...to which the iModule will connect Insert the PSK name of Wi Fi network to which the iModule will connect Ignor the following 4 fields Insert Static IP Address Insert Static NetMask Insert Static GW Ad...

Page 11: ...section are addressed to all those who will use the machine The machine must be used and accessed only by qualified operators that fully read and understood the User section paying particular attentio...

Page 12: ...onse code below Or find the APP iMODULE directly in App Store for iOS Apple iPhone iPad Google Play for Android Once you have installed the APP iMODULE you can access the DEMO version username and pas...

Page 13: ...UAL mode only 2 Green LED Steadily Lit MANUAL mode enabled boiler controlled by the Local Controller Flashing Slowly AUTOMATIC mode enabled boiler controlled by the APP iMODULE Flashing Quickly MANUAL...

Page 14: ...rsion send an SMS to configure the APN Green Slow Flashing LED 1 flash every 2 5 seconds MANUAL mode enabled boiler controlled by Local Controller Green Slow Flashing LED 1 flash every second GSM Wi F...

Page 15: ......

Page 16: ...RADIANT BRUCIATORI S p A Via Pantanelli 164 166 61025 Montelabbate PU Tel 39 0721 9079 1 fax 39 0721 9079279 e mail info radiant http www radiant it...

Reviews: