10
1300905-W2-A
Temperature
Minimum Cold Water Temperature:
1°C
Maximum Hot Water Temperature:
70°C*
Factory Preset:
43°C
under ideal installation conditions
Optimum Thermostatic Control Range:
35°C - 46°C
*Note!
For optimum performance reasons it is recommended that the maximum hot water
temperature is limited to
65°C.
Caution!
During thermal disinfection the mixing valve can operate up to
85°C
for short
periods. Ensure safety precautions are followed during discharge. Chemical disinfection
agents e.g.chlorine/chloramines combined with higher temperatures will affect the life of the
product adversely and could detrimentally affect the thermostatic performance.
Flow Rates
Minimum Flow Rate:
6 l/min
at mid blend with nominally equal supply pressures.
Maximum Flow Rate:
120 l/min
Flow Control
Rada 320 mixing valves do not have integral flow control; appropriate provision must be made
for this in the outlet pipework. This can be in the form of a stop-cock, mechanical timed-flow
controller, solenoid or basin/bath tap. The device chosen must be non-concussive in operation.
Connections
320 IC
- Inlets & outlet connections: 28mm compression.
320 IF
- Inlets & outlet connections: 1” BSP female thread.
320 F
- Inlet & outlet adaptors 1” BSP female thread.
320 M
- Inlet & outlet adaptors 3/4” BSP male thread
.
Flow Rate/Pressure Loss Graph
Flow Rate/Pressure Loss Graph
Flow Rate Litres/Mi
n
Pressure Loss - bar
20
80
0
1.0
3.0
4.0
2.0
60
40
0
100
120
6.0
5.0
Summary of Contents for 320
Page 1: ...1 1300905 W2 A 320...
Page 3: ...3 1300905 W2 A X 1 q X 1 q X 1 q X 1 q 320 IC X 3 q X 2 q X 1 q X 1 q X 2 q...
Page 4: ...4 1300905 W2 A 320 IF X 1 q X 1 q X 1 q X 1 q X 2 q X 1 q X 1 q X 2 q...
Page 5: ...5 1300905 W2 A 320 F X 1 q X 1 q X 1 q X 3 q X 1 q...
Page 6: ...6 1300905 W2 A 320 M X 1 q X 1 q X 1 q X 3 q X 1 q...
Page 12: ...12 1300905 W2 A a b 6 0 mm 2 1 3 0 mm 6 0 mm 3 0 mm 6 0 mm...
Page 13: ...13 1300905 W2 A 3 320 IC 320 IF Install the connections...
Page 14: ...14 1300905 W2 A 320 M 320 F 4 1 min...
Page 15: ...15 1300905 W2 A 5 3 0 mm 6 320 IC 320 IF Install the pipework a...
Page 16: ...16 1300905 W2 A 320 M b c 320 F...
Page 29: ...29 1300905 W2 A...