It is highly recommended to change default password (admin) even if the user name remains always
the same (admin). When the Apply button is pressed, the unit reboots.
7.6.5. Miscellaneous
•
Reboot
– when pressed, the unit correctly shuts down and starts again (performs the cold start
which equals to a power cycle). The reboot time is approx. 25 sec.
7.6.6. SSL certificate
It is possible to download your own SSL certificate into RipEX for https communication used for web
configuration. 2048 bits certificate is supported and recommended, however the 512 or 1024 bits certi-
ficates can also be used. SSL certificate may have one or two files. Both options are supported.
•
Certificate file
Fill in the Certificate file, or browse your disk in order to find the file.
•
Key file
When your SSL certificate consists of two files, fill in the Key file, or browse your disk in order to find
the file.
When file(s) is selected, it can be uploaded.
•
Upload
– when pressed, the selected Certificate is uploaded into the RipEX, however it is not active
yet.
•
Apply
– when pressed, the uploaded certificate is activated. Afterwards the unit automatically reboots
itself.
•
Default
– when pressed, the default RACOM SSL certificate is uploaded. To be activated, Apply
button has to be executed.
7.6.7. RF transmission test
It is intended to be used for laboratory measurements or antenna testing.
•
Type
List box: Carrier, Random data
Carrier – only unmodulated carrier is transmitted
Random data – modulated random data is transmitted
Default = Carrier
•
Period [s]
Default = 15 s (possible values 1s – 50s)
During this time period RipEX transmits after Start button is executed.
7.6.8. Technical support package
Fig. 7.20: Menu Maintenance Configuration
RipEX Radio modem & Router – © RACOM s.r.o.
140
Advanced Configuration