Priority 

path: Settings > Startup Delay & Outlet Importance 
 
The 

Importance

 column gives a rating from 1 to 8 to each outlet. A rating of 1 indicates the 

highest importance, whilst 8 is the lowest. 
When the Total (device) off threshold for the amperage and/or wattage is crossed (but none of 
the individual off thresholds) the EnergySwitch will use the importance rating to determine which 
outlet to switch off first. 
If two or more outlets have the same rating, the outlet with the last peak load will be switched 
off first. 

Overheat Protection 

path: Settings > Overheat Protection 
 
The EnergySwitch has built in temperature sensors that can help prevent overheating. For more 
information regarding the thresholds and event notifications please refer to the Thresholds and 
SNMP Configuration chapters. 
 

Note:   

The EnergySwitch has a built-in safety that switches off all ports when the temperature 
hits 60°C (140°F) 

regardless

 of the settings in the Overheat Protection section. 

Network Time Protocol (NTP) 

path: Settings > Device Settings 
 
The Network Time Protocol (NTP) is a protocol for synchronizing the clocks of computer systems 
over networks. The EnergySwitch is equipped with an onboard clock that can be setup to sync 
with: 

 

pool.ntp.org (default) 

 

a custom NTP server 

 

date & time picker 

 
For more information regarding the configuration of the onboard clock please refer to the Device 
Settings chapter. 

Summary of Contents for ES1100 Series

Page 1: ...User Manual ES1000 Series ES1100 Series EnergySwitch...

Page 2: ...fications 9 Safety 10 Certifications 11 Compliance 11 Recycling 12 Servicing Repair 12 Additional Documentation 12 Getting Started 13 Receiving Inspection 13 Inventory 13 Installation 14 Rack Mounting...

Page 3: ...Power 28 Environment 28 Logging 28 Modules 28 Management 29 Settings 29 Network Configuration 30 SNMP Configuration 31 SNMP Settings 31 Device Settings 32 Thresholds 32 Resetting Measurements 34 Start...

Page 4: ...ce 44 EnergySwitch Configuration 47 Logging 49 Event 49 Measurement 49 Management Information Base MIB 51 Upgrade Firmware 52 Obtaining Files 52 Troubleshooting 53 Downloading the diagnostics 53 Reset...

Page 5: ...to the future of data center energy management leveraging leading edge EnergyDNA for highly granular visibility into rack based energy quality and consumption Main Features Real Time True RMS measurem...

Page 6: ...esteenweg 19 9080 Lochristi Belgium www racktivity com v 2013 10 7 Applicable Models Unless specified otherwise all information in this document is applicable to the following Racktivity EnergySwitch...

Page 7: ...urrent total 16A Current per C13 8A The model number input and output ratings and certification information for the EnergySwitch are also shown on the label found on the case of the unit Operating Env...

Page 8: ...s Open CLI session Yes Yes Yes View current status states data values Yes Yes Yes Toggle outlets Yes Yes No Edit thresholds Yes No No Edit outlet names Yes No No Change SNMP notification settings Yes...

Page 9: ...le unless noted otherwise Cisco Cisco devices that have a Console which uses the pin lay out of the 72 3383 01 Management cable RJ45 DB9 Hewlett Packard HP devices that have a Console which uses the p...

Page 10: ...nd plug are in good condition Do not connect the EnergySwitch to an ungrounded utility power outlet Do not operate your EnergySwitch with any covers removed or when it is damaged This EnergySwitch con...

Page 11: ...ser replaceable Certifications Not all certifications are applicable to every model Please check the label on your device CE FCC This device is designed in compliance with the requirements of the 4 fo...

Page 12: ...g Repair There are no user serviceable parts inside the EnergySwitch All repairs and service should be performed by authorized service personnel only Please refer to the Service manual for RMA procedu...

Page 13: ...received Report any damage immediately to the shipping agent and report missing contents damage or other problems immediately to your reseller Inventory Please verify the contents of the box Standard...

Page 14: ...It is recommended that 2 5cm 1 inch of clearance be supplied around the sides of the unit Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not ach...

Page 15: ...included power cord to the EnergySwitch by inserting the input cable in to the power inlet Note Optionally a user supplied power cord can be attached to the EnergySwitch by connecting it to the IEC i...

Page 16: ...ce connector 3 RS232 8 x RS232 Out of Band management connectors 4 LAN Ethernet connector with connectivity indicator LEDs 5 OUTLET LEDs 8 blue outlet status LEDs 6 STATUS LEDs Alarm and power LEDs 7...

Page 17: ...2011 Racktivity NV 17 55 Antwerpsesteenweg 19 9080 Lochristi Belgium www racktivity com v 2013 10 7 Rear Panel 1 INLET Power inlet 2 OUTLET 8 Power outlets 3 OUTLET LEDs 8 blue outlet status LEDs...

Page 18: ...N The corresponding outlet is turned on OFF The corresponding outlet is turned off and the connected device is not receiving input power Alarm LED ON Warning at least one alarm visit the Web Interface...

Page 19: ...through a selection list in the menus Press OK to select the highlighted item and MENU to go back When in a menu the symbol indicates that clicking this item will open a submenu The symbol indicates...

Page 20: ...default Use https instead of http in your browser to access the web portal Firmware version 1 2 or higher Dynamic IP Address Assignment DEFAULT 1 Press the MENU button until the MAIN menu appears sel...

Page 21: ...t password is 1234 Manual IP Address Assignment 1 Obtain the correct IP address standard gateway DNS Server IP and subnet mask from your network administrator 2 Press the MENU button until the MAIN me...

Page 22: ...ess OK Press the MENU button to cancel or the OK button to apply the settings 8 On a computer in the same network use a browser to open the chosen IP address for example https 192 168 14 250 When surf...

Page 23: ...K menu 5 Press UP to select CURRENT IP ADDRESS The assigned IP address is shown in yellow at the bottom of the TFT 6 On a computer in the same network use a browser to open the assigned IP address for...

Page 24: ...nd press OK 6 Use the UP and DOWN buttons to change the currently selected value and press OK to select the next value When holding the UP and DOWN buttons changing the values speeds up When ready pre...

Page 25: ...55 Antwerpsesteenweg 19 9080 Lochristi Belgium www racktivity com v 2013 10 7 When surfing to the web portal a popup appears requesting a username and password The default username is admin and the de...

Page 26: ...ve not been fully tested by Racktivity Logging in For instructions on how to set up the TCP IP settings to connect to the Web Interface please see the Network Settings chapter To recover from a lost p...

Page 27: ...d off GREEN the outlet is on and working normally ORANGE a warning threshold has been crossed but the port state has not yet changed only visible on the Overview tab and the affected parameter s tab R...

Page 28: ...g Control fuse and or line currents Oscilloscope view for an outlet Overview of connected Agents Environment Use the Environment Tab to monitor and manage Internal sensors as applicable Voltage status...

Page 29: ...itch setup including Energy Sensors For more information regarding the managing of Energy Sensors please see the Energy Sensor documentation Available as of firmware version 1 2 Settings Use this tab...

Page 30: ...f the EnergySwitch Subnet Mask o The subnet mask of the EnergySwitch Standard Gateway o The IP address of the default node on the network DNS Server o The IP address of the Domain Name System DNS serv...

Page 31: ...elated settings can be found in the Network Configuration chapter The following SNMP settings are editable SNMP Community read The community read string for GET requests SNMP Community write The commu...

Page 32: ...heit F Clock settings see the Network Time Protocol NTP chapter o Date Time Settings The real time clock dialog features several options Uncheck the Use NTP checkbox to be able to set a custom date ti...

Page 33: ...gled off and an SNMP notification is sent Low When the measurement goes below this value an SNMP notification is sent High When the measurement goes above this value an SNMP notification is sent To ch...

Page 34: ...kWh counter is not resettable o path Power Energy Individual total Apparent Energy kVAh o Note The Accumulated kVAh counter is not resettable o path Power Energy Temperature o path Environment Ambien...

Page 35: ...Settings Overheat Protection The EnergySwitch has built in temperature sensors that can help prevent overheating For more information regarding the thresholds and event notifications please refer to...

Page 36: ...Connection settings 115200 8 N 1 115200Bd 8 data bits no parity 1 stop bit Telnet Connect to the device IP on port 23 over Telnet Please note that only Telnet over SSL is enabled by default This can b...

Page 37: ...elgium www racktivity com v 2013 10 7 Note The complete CLI interface is available as from firmware version 1 1 x x Version 1 0 x x and below only have a reduced interface or less For more information...

Page 38: ...iled info to open RS232 port 4 at 19200 Baud the command would be OPENCOM c4 b19200 Open a new telnet session to the EnergySwitch on port 2000 and login You are now connected to the desired RS232 port...

Page 39: ...Configuration Compatible Devices The following UPS models can be linked to your EnergySwitch PDU Most APC Smart UPS models except Microlink enabled devices Connecting the UPS The EnergySwitch and the...

Page 40: ...0 Lochristi Belgium www racktivity com v 2013 10 7 CLI Specifications chapter connected to the CLI connector on the front of the unit On the side of the UPS a DB9 male connector RJ45 DB9 Function Pin...

Page 41: ...gySwitch will perform automated actions according to strict pre defined rules based on battery level UPS status etc Please review these rules and actions carefully to avoid unexpected behavior Operati...

Page 42: ...igured the EnergySwitch will perform automated actions according to strict pre defined rules based on battery level UPS status etc Please review the following rules and actions carefully to avoid unex...

Page 43: ...evel dropped below the UPS Emergency Threshold and the UPS is running on mains power again and the Battery Level goes above the UPS Recovery Threshold All powered outlets and outlets marked with Preve...

Page 44: ...service on the connected devices 2 Configuring the EnergySwitch to communicate to the installed Agent WARNING If both UPS Integration is enabled and Agent Communication is correctly configured the Ene...

Page 45: ...s x86 Racktivity agent ini Linux etc racktivity agent ini Configuration The agent ini file contains the following sections and editable parameters MAIN host The IP on which the Agent listens 0 0 0 0 m...

Page 46: ...ng on the configuration Example reboot reconfigure Sets a configuration parameter on the agent side Example reconfigure shutdown url disabledA0B1C2D3E4F5G6H7I8J9 In the example we set the URL paramete...

Page 47: ...f manually and with UPS integration enabled will be managed differently see the Rules chapter for more information Mostly used for vital rack equipment Agent IP IP of the machine where the Agent for t...

Page 48: ...lso be sent to an associated agent manually through the use of an HTTP API when logged in as administrator https DEVICE_IP agent cgi ADDR P X INDEX Y CMD z o DEVICE_IP IP of the PDU o X Number of the...

Page 49: ...log Download Download the log as a text file Show View the log in your browser The Log is displayed as a table with the following columns from left to right Timestamp The timestamp of the event Event...

Page 50: ...Antwerpsesteenweg 19 9080 Lochristi Belgium www racktivity com v 2013 10 7 Module The module for which to request the log Start time The starting date time End time The ending date time Download Downl...

Page 51: ...n v1 3 x x and above https DEVICE_IP ES RACKTIVITY MIB txt A direct link to the MIB file is also available under Settings Network Settings For firmware version v1 2 x x and above https DEVICE_IP ES RA...

Page 52: ...update the device continues working as normal Note Make sure all active connections to the EnergySwitch such as the website telnet and SNMP are closed before updating Open connections might result in...

Page 53: ...l now be reset to their default settings Default login credentials User name admin Password 1234 Connecting to the Web Interface If you are unable to connect to the Web Interface please try one or mor...

Page 54: ...gium www racktivity com v 2013 10 7 Press MENU to enter the Menu Select Network or Network Settings v1 2 and press OK Press the DOWN button and select Current IP address or IP Address v1 2 The IP of y...

Page 55: ...g 19 9080 Lochristi Belgium www racktivity com v 2013 10 7 Support Feel free to contact us if you need any support or have any other questions or remarks Online www racktivity com support E mail suppo...

Reviews: