Wire Diagrams
Caution
:
■
TURN OFF ALL POWER BY
REMOVING THE POWER FUSES
OR TURNING OFF THE CIRCUIT
BREAKER FOR YOUR SAFETY
AND TO PREVENT DAMAGE TO
THE UNIT.
■
The ground wire must be tightly
secured to ground.
3-Way Switch Wiring Diagram
Basic Wiring Diagram
Single Level Lighting
Multiple Level Lighting Wiring
Diagram
3-way Switch wiring Diagram
BLACK
BLACK
RED
RED
BLACK
BLACK/HOT
WHITE/COMMON
LOAD
GREEN
Basic Wiring Diagram
Single Level Lighting
COMMON (WHITE)
HOT (BLACK)
RED
LOAD
Multiple Level Lighting
Wiring Diagram
RED
COMMON (WHITE)
HOT (BLACK)
LOAD
LO AD
LO AD
3
Time Delay Adjustment
The time delay adjustment can be set
so the lights turn off from 30 seconds
minimum to 30 minutes maximum
after the room is vacated.
Walk Test
To test the detection pattern of the
LOS1000 make no motion for 30
seconds. Move sideways up to 12”.
The red LED should blink. If you move
continuously, the LED will blink once
every 2 seconds. The LOS1000 is
factory set at optimum detection, so
no field adjustment is required.
Bypass Key
When the bypass key is inserted
into the slot, the lights will always
be on. This key is recommended for
emergency use only.
Field of View Adjustment
If the sensor is “seeing” out through
a doorway into a hallway or “seeing”
undersired areas, simply cover part
of the sensor lens with opaque white
tape or a paper label. Clear tape
may be used, but it limits detection
only partially. Test that the portion of
the lens covered limits detection as
desired and does not reduce detection
in other areas
.
Removing the Adjustment
Access Cover:
This cover is tamperproof and cannot
be removed if the switch cover plate
is attached. The cover has two “ears”
that hook under the cover plate and
prevent tampering. To remove the
cover, insert a screwdriver into the
latch and pull forward.
Insert small
screw driver
into slot and
pull forward
Hole f or
Coverplate screw
Mounting screw
Mounting screw
LED for walk
testing detection
indicator
Motion
Sensor lens
Auto/Off switch
auto (In) Off (Out)
Time delay
(30 second minimum
15minute maximum)
Turn the control
gently clockwise
with a small
screwdriver for
more time delay.
Hole for
Coverplate screw.
Over tightening
screw will strip
threads .
Bypass Key
4
Adjustments
6
7