8 - Edition 10/2014 Cod. 2200780113  01 - 

 

15.3 CLEANING THE CONDENSER (Fig. 10)

 

 

The condenser must be cleaned every month. 
Proceed as follows: 
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 10 
- Turn on the supply automatic differential switch Ref. 4 Fig. 10 

- Remove the panels Ref. 5 Fig. 10  
- Clean the condenser fins Ref. 1 with compressed air (Fig. 10) 

DO NOT USE WATER OR SOLVENTS

 

- Close the panels Ref. 5 Fig. 10

  

 

16.0 SCRAPPING THE UNIT 

If the machine is to be scrapped, it must be dismantled into parts of the same material, to be disposed of according to the local regulations 

in force. 

 

ALWAYS RESPECT THE REGULATIONS IN FORCE FOR DISPOSING OF OLD OIL AND OTHER POLLUTING MATERIALS SUCH AS 
INSULATING FOAM, ETC. 

 

17.0 TROUBLE-SHOOTING AND EMERGENCY REMEDIES 

 

 

ALL WORK MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL. BEFORE CARRYING OUT ANY MAINTENANCE 
JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE POWER MAINS. 

 

N.B.  OPERATIONS MARKED  



  MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL APPROVED THE 

MANUFACTURER

 

 

FAULT FOUND

 

POSSIBLE CAUSES

 

OBSERVATIONS

 

1)

 No compressed air passes through  the dryer 

outlet 

 

1A)

 The pipes are frozen inside  



 -The bypass valve of the hot gas    is broken or 

out-of-calibration 

      -The room temperature is too low  and the 

evaporators piping are  obstructed with ice  

2)

 Presence of condensate in the  pipings. 

2A)

 The condensate separator does not work 

correctly 

 

 

2B)

 The dryer is working outside its rating  

 
 

 

2C)

 The dryer is working under bad conditions of 

condensation  

      - Clean the filter from  the condensate drain 



-Check the condensate drain 

 

 
      -Check the flow rate of treated air 

      -Check the room temperature 
      -Check the air temperature at the drier inlet. 

       
     -Clean the condenser. 



-Check the good operation of the   fan. 

3)

 The compressor head is very hot  

    > 131 °F (55 °C) 

      Make reference to 

2B

 

      Make reference to 

2C

 

3A)

 The cooling circuit is not working with the right 

gas charge 

 

 



 -Check if there are leaks of refrigerating gas. 



 - Charge it again. 

4)

 Motor cuts out on overload 

       Make reference to 

2B

 

       Make reference to 

2C

 

       Make reference to 

3A

 

 

5)

 The motor hums and does not start. 

       The line voltage is too low. 

       You switched the machine off and  on again 

without leaving enough time for the pressure 

balancing. 

       The starting system of the motor is defective. 

      -Contact the electric power  company 

      -Wait a few minutes before starting the machine 

again. 

 



 -Check the running and starting  relays and 

condensers (if any) 

6)

 The compressor is very noisy. 

      Troubles with the internal mechanical parts or 

with the valves 

 

 

 

 
 
 
 
 
 
 
 
 

Summary of Contents for QPNC 10

Page 1: ...PY OF THE WIRING DIAGRAM INSIDE THE ELECTRIC PANEL ADDRESSES OF ASSISTANCE CENTRES In the event of breakdown or malfunction of the dryer switch it off and do not tamper with it If repairs are needed a...

Page 2: ...mans or used on direct contact with foodstuffs These uses are allowed if the compressed air produced is filtered by means of a suitable filtering system Consult the manufacturer for these special uses...

Page 3: ...The removal of or tampering with the safety devices constitutes a violation of the European Standards on safety ALL WORK ON THE ELECTRIC PLANT HOWEVER SLIGHT MUST BE CARRIED OUT BY PROFESSIONALLY SKI...

Page 4: ...ter removing the packing ensure that the machine is unbroken and that there are no visibly damaged parts If you are in doubt do not use the machine but apply to the manufacturer technical assistance s...

Page 5: ...LURE TO COMPLY WITH THESE NDICATIONS CANNOT BE ATTRIBUTED TO THE MANUFACTURER AND MAY CAUSE INVALIDITY OF THE GUARANTEE CONDITIONS 12 4 STARTING UP See part B of this manual Chpter 18 0 13 0 DIMENSION...

Page 6: ...15 F 46 C Inlet air temperature 100 F 38 C Min ambient temperature 34 F 1 C Working pressure 102 psi 7 bar Max inlet air temperature 131 F 55 C Dew point in pressure 39 F 4 C Max working pressure 232...

Page 7: ...Monthly Condenser Clean the condenser fins to remove eventual dust 15 2 CLEANING OF THE AUTOMATIC CONDENSWATER DISCARGER FILTER Fig 10 Clean the filter of the steam trap Proceed as follows Close the c...

Page 8: ...s are frozen inside The bypass valve of the hot gas is broken or out of calibration The room temperature is too low and the evaporators piping are obstructed with ice 2 Presence of condensate in the p...

Page 9: ...probe failed replace probe Warning icon NOT fashing label H2 flashing High PDP call for service refrigerant leak flow rate inlet temperature exeeding the limit Warning icon NOT fashing label L2 flash...

Page 10: ...H 10 Edition 10 2014 Cod 2200780113 01 SE ALARM After 2000Hrs the controller will issue a SE warning This is the maintenance due warning How to reset the maintenance warning follow steps 1 to 6 1 2 3...

Page 11: ...fore starting it again wait at least 5 minutes in order to allow the pressure balancing BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE POWER M...

Page 12: ...ENGLISH 12 Edition 10 2014 Cod 2200780113 01...