Installer Supplied Items

Refrigerant Line Set : Flare Connection only, suitable for R410A with both lines insulated, max length 50ft
Units manufactured prior to May 2007 do not include the female flare nuts for the refrigerant line sets
Main System Breaker : Sized per unit requirements, to be mounted adjacent to Outdoor unit
High Voltage Interconnect Wiring : 14 AWG wiring from Outdoor unit to Indoor unit for Power and Control
Mounting Hardware : Wall Anchors, Condenser Pad etc
Refrigerant : R410A required for additional line set charge
Condensate Piping : Per local codes to remove condensate from the indoor unit

Items for Consideration

Application 

Check the application of the unit prior to installation, certain applications require additional components or 
installation parameters

Computer or Data Server Rooms, 

These require ballpark sizing of approximately 12,000 Btu/h Capacity per 250 SqFt of room size
The units will be running 24/7, so a Low Ambient Head Pressure Controller (See accessories), a Crankcase
Heater and possibly a Wind Baffle (Field Supplied for cooling below 32 DegF) 

must

 be installed

Offices and Commercial Spaces, Churches etc

These require ballpark sizing of approximately 12,000 Btu/h Capacity per 400 SqFt of room size
The units could have the possibility of providing cooling with ambient's below 65 DegF, so a Low Ambient 
Head Pressure Controller (See accessories) is required as is a Crankcase Heater (field supplied)

Residential, Bedrooms, Family Rooms etc

These require ballpark sizing of approximately 12,000 Btu/h Capacity per 600 SqFt of room size
Low Ambient is typically not needed, unless a home office application is required.
Heat Pumps are a great application, however the units do not feature any back up resistance heat, so we
do not recommend their use as a primary source of heat in areas where the winter temperatures fall below
25 DegF.

Installation

Determine the best location for mounting the Indoor unit, it must be located a minimum of 4 ft from the floor
Pay attention to the air circulation in the room, 9 & 12k units throw air 15ft, 18 & 24k units throw air 25ft, ensure 
no obstacles to airflow exist

Locate the Indoor and Outdoor units as close together as possible, maximum line set run and lift 

CANNOT

BE EXCEEDED

, then determine how the Interconnect piping, wiring and condensate hose is to be run

Unit 

QSCE-09/12
QSCE-18/24
QSHE-09/12
QSHE-18/24

Ensure that all panels can be removed for service as required

Certification

All Quietside Ductless Mini Splits are certified by UL under UL standard 1995 in both Canada and the US
Performance is certified by our certification under the ARI 210/240 Program

Installation and Maintenance Manual

3/8" & 5/8"

20 Feet
20 Feet

50 Feet
50 Feet
50 Feet
50 Feet

3/8" & 5/8"

20 Feet
20 Feet

1/4" & 1/2"

Max Line Set Run

Max Vertical Lift

Line Sizes

1/4" & 1/2"

Summary of Contents for QSHE-092

Page 1: ......

Page 2: ......

Page 3: ......

Page 4: ......

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...manual 1 Check Rating Plate for correct system voltage before installing the unit Installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void th...

Page 16: ...t s below 65 DegF so a Low Ambient Head Pressure Controller See accessories is required as is a Crankcase Heater field supplied Residential Bedrooms Family Rooms etc These require ballpark sizing of a...

Page 17: ...ide recommend the Aspen brand of Condensate Pump follow their wiring diagram recommendations This pump is installed externally to the unit Follow Instructions failure to follow instructions may cause...

Page 18: ...ng the weight of the unit Use a level to ensure mounting bracket is leveled so condensate can drain properly Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 9...

Page 19: ...set between the Outdoor unit and the Indoor unit MUST have both refrigerant lines insulated as condensing device is located in the Outdoor unit Gently bend the line set stubs from the Indoor unit to...

Page 20: ...system installed must have a separate branch circuit with an individual breaker fuse QCIC 09 QCIC 12 QCIC 18 QCIC 24 Breaker Size 15A 15A 15A 20A RLA 6 7A 8 8A 5 3A 8 6A MCA 8 2A 10 8A 6 5A 10 6A QCIH...

Page 21: ...is required then cut the lead and extend it using 18 AWG thermostat wire Sensor is resistance based using 3 5V DC Defrost Sensor wire connection in Outdoor unit is accessed by removing top panel from...

Page 22: ...ture is above 65 DegF to prevent damage to the compressor Unit has a 3 minute time delay for the compressor start up operation Unit is charged with enough R410A refrigerant for a line set of 25ft leng...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Reviews: