background image

 

Quest IQ Compressor Wall OMM

 

18

 

 September 2020

 

 

Based  on the premise air temperature, the Reheat and AC valves would adjust their opening position (open 
more/close more), reducing or increasing fluid flow to and through the respective fluid coils: 

 

Reheat and AC valves are controlled in the same manner with opposite effect: for example, 
when AC valve opens 10% more, Reheat valve closes 10% more etc.  

o

 

if more heat is required by the room air, the Reheat valve opens more, and AC valve closes more, thus 
diverting more fluid to the reheat coils (heat is rejected to the premise);  

o

 

if more cooling is required by the room air, the AC valve opens more, and Reheat valve closes more, 
thus diverting more fluid to the dry cooler (heat is rejected outdoors).  

o

 

Outdoor dry cooler fans are engaged only if at least some fluid is diverted towards outdoor dry cooler 
and compressor pressure is higher than pre-set level (see 

Outdoor Dry Cooler Operation

 below).

 

 

Once demand for the compressor’s operation is removed (respective call is satisfied), the pump down solenoid 

valve  closes;  once  the  compressor  suction  pressure  reaches  the  pre-set  pressure,  the  glycol  pump  and 
compressor stop. 

 

Outdoor Dry Cooler Operation.

  

Respective signal(s) are sent by control system to engage EC-type fans via a variable 0-10VDC signal (proportional 
to the compressor head pressure level). Refer to the wiring diagram if/when needed. 

If the dry cooler is equipped with the built-in pump package (to establish cooling fluid flow between HVAC system 
and the dry cooler or to serve as additional/booster pump), the said pump is also engaged along with dry cooler 
fans 

 

pump would stay engaged while fans are engaged (regardless of the fans’ speed

).  

 

Economiser Option (Eco-Coil).  

HVAC system, equipped with eco-coil and dry cooler, can take an advantage of economiser option and use outdoor 
air to cool the premise without resorting to compressor operation.  

 

When Air Conditioning (cooling) mode is requested and outdoor air conditions warrant (outdoor air and, 
respectively, cooling media in the dry cooler are cool enough), ECV (eco-coil mixing valve) would divert 
cool media from dry cooler into eco-coil, thus cooling recirculating air without running the compressor. 

 

 

Summary of Contents for IQ Compressor Wall Series

Page 1: ...IQ SERIES Compressor Wall OPERATION AND MAINTENANCE MANUAL QuestClimate com GROW ROOM HVAC...

Page 2: ...ta 9 Layout and Components 10 HVAC system Main Components 10 Control System 13 Dry Cooler Layout and Components 14 Sequence of Operation 16 Set Points 16 Ventilation 16 Space Heating 16 Air Conditioni...

Page 3: ...ly qualified technicians should install operate maintain or service mechanical equipment including current dehumidification system Read this manual before performing any tasks to familiarize yourself...

Page 4: ...ractors WARNING Any work installation start up service maintenance repair etc on any mechanical equipment HVAC system dry cooler etc must be performed in accordance with manufacturer s recommendations...

Page 5: ...and Options Standard AG series HVAC systems are semi custom while basic concept and layout is the same options and specific systems and components layout and location may vary from one HVAC system to...

Page 6: ...th the HVAC system Packaged AC option is available for outdoor models only alternatively indoor and outdoor models could be fitted for separate remote AC option remote dry cooler or other external coo...

Page 7: ...ly refer to submittal documentation Space Heating Gas Heater connection gas line If the HVAC system is equipped with a gas heater boiler gas furnace etc for space heating purposes the gas line connect...

Page 8: ...ystem s submittal documentation for more details Standard dry coolers used with this model of HVAC system is NG V series composed of number of two coils two fans blocks based on required capacity of t...

Page 9: ...nces Proper clearances should be maintained for adequate airflow and heat rejection Generally up to 36 side and 96 top clearances are required For more information on clearances as well as equipment d...

Page 10: ...interior of the HVAC system to show External systems connections location direction space heating cooling circuits condensate Air filter locations quantity and size Additional Info warning caution sti...

Page 11: ...on a Quest product is technically possible If provided the EF assembly is located on the HVAC system s return air side Exhaust Air opening in outdoor installed HVAC system is equipped with louver s 76...

Page 12: ...September 2020 11 Quest IQ Compressor Wall OMM 1 2 76 9 7 8 11a 21 24...

Page 13: ...self contained refrigerant circuit within each module Each module also includes a Control Module 17 Common to the compressor modules is the Glycol Pump 16a that circulates water glycol to reject compr...

Page 14: ...arious temperatures air water compressor etc b Combo sensor is used to monitor air temperature and humidity Compressor operation is monitored with pressure sensors Pic D 3 c Pressure Transducers only...

Page 15: ...l applicable AC options there are some deviations number of fans composition etc Refer to AC Options Basic View Basic Information chapter for additional information Cooling AC coils 31 where heat from...

Page 16: ...te side of the dry cooler Dry Coolers Pump Package Dry Coolers if equipped with such option would have a pump package box Pic D 6 below shows general layout of pump packages used for NG V model dry co...

Page 17: ...tively If such option is used exhaust fan speed would be controlled like the main blower via adjustable pre set variable signals the exhaust fan speed may vary depending on scheduled ventilation mode...

Page 18: ...shown on Pic E 2 Schematic shows single compressor module additional compressor modules schematic is the same and common to all compressor modules glycol cooling circuit Compressor operation below app...

Page 19: ...ive call is satisfied the pump down solenoid valve closes once the compressor suction pressure reaches the pre set pressure the glycol pump and compressor stop Outdoor Dry Cooler Operation Respective...

Page 20: ...ng the HVAC system and or performing any equipment maintenance work make sure that all moving parts are stopped and it is safe to perform required task Maintenance Key Points Here are some basic key m...

Page 21: ...ired Check and tighten if required hose clamps and sensor mounts Inspect all airside coils dry cooler HVAC system coils evaporator etc for dirt cobweb build up etc clean as needed Check that the P tra...

Page 22: ...Warning Hazardous chemicals Cleaning agents can be highly acidic or alkaline Handle all chemicals carefully and use appropriate personal protective equipment PPE Refer to the cleaning agent manufactu...

Page 23: ...r air bleeding valve etc Have each local low point of the system equipped with means to drain the fluid CAUTION Draining and re filling the dry cooler must be performed by trained personnel according...

Page 24: ...Warranty During the first 90 days from initial start up all parts and repairs related to factory defects or replacement parts are covered by the Quest manufacturer warranty All parts and labor requir...

Page 25: ...cts on which payment is in default 2 Parts that wear out due to normal usage such as air filters fuses and sensors are not covered by this warranty NOTE Refrigerant lost during the Initial 90 day Comp...

Page 26: ...ts must be returned to the factory with transportation prepaid by the customer as a condition of these warranties Optional extended warranties are for parts only and subject to all the terms of the Tw...

Reviews: