9.0
Specifications
Power
Interoperability
Communication
BACnet MS/TP
BACnet Profile
B‐ASC
Baud Rate
9600, 19200, 38400, 57600, 76800 bps
MAC Address
BACnet MS/TP MAC Address;
Adjustable from 1 – 127
Network Address
BACnet Net Address;
Adjustable from 1 – 4194
Hardware
Memory
Flash Memory
Backup
Battery good for 6 months
Environmental
Operating Temperature
0C to 50C;32F to 122F
Storage Temperature
‐30C to 50C;‐22F to 122F
Relative Humidity
0 to 95% non‐condensing
Enclosure
Color
Quest White
Dimensions
3.65” x 5.30” x 1.5”
(300mm x 200mm x 100mm)
Shipping Weight
0.75lbs (.34kg)
Agency
Approvals
UL
UL873 (US) and CSA C22.2 No.24 (Canada)
FCC
Compliant to CFR 47, Part 15, Subpart B,
Class A (US)
CA
Title 24
Inputs
Digital Input
Relay dry contact only across
C terminal to DI1
Zone & Supply
10K Type 3 thermistor
CO2 (future)
Outputs
Contact Output Rating
Each relay output (G, Y1, Y2, W1/B, W2, O)
has: 30V AC, 1 A maximum 30V AC, 3A in‐rush
Analog Output (future)
0‐20mA or 0‐10V DC
LCD
Display
Type
Backlit LCD display
Display Area
2 rows of 16 characters each
Functionality
Resolution
‐Temperature
+/‐0.1C(+/‐0.2F)
‐Humidity*
‐CO2*