1.0 Overview 

The Quest Controls Lead/Lag control thermostat is designed for controlling two single stage HVAC 
systems.  It is an easy to use thermostat for remote shelters that require a simple to use lead/lag 
controller with a wide profile operating range for cooling. 

1.2 Features and Benefits 

 

Controls two single-stage HVAC systems for Fan, Cool and Heat. 

 

Powered from the HVAC 24VAC transformers. 

 

Automatic lead change every 24 hours. 

 

LCD display for current operating mode and shelter temperature readings. 

 

Comfort mode to allow “Occupied” settings for a 

one hour timed duration. 

 

Five button keypad for navigation to other status screens. 

 

Built in zone temperature. 

 

All configurations and setpoints are stored in non-volatile flash memory and are not field 
changeable. 

2.0 Installation / Wiring 

The T-Stat LLC is a simple application specific controller designed to control two Single -Stage 
Conventional HVAC systems. 

1-1/16"

1-1/2"

2-1/4"

3-1/4"

Back mounting plate 5-3/8", 5-1/2" with cover

B

a

c

k

 m

o

u

n

ti

n

g

 p

la

te

 3

-5

/8

",

 3

-7

/8

w

it

h

 c

o

v

e

r

1-9/16"

1/2"

UP

 

Figure 1 

 Back Plate Mounting 

Summary of Contents for 100 T-Stat LLC

Page 1: ...NOTICE Copyright 2018 by Quest Controls Inc QUEST The material discussed in this publication is the proprietary property of QUEST QUEST retains all rights to reproduction and distribution of this pub...

Page 2: ...0 Installation Wiring 4 2 1 Installing the mounting plate 5 2 2 Wiring 5 3 0 Front Panel Display Keypad Operation 7 3 1 Run Mode 7 3 2 Occupied Override 7 3 3 Lead Switch 7 3 4 T Stat Settings 8 4 0 C...

Page 3: ...credentials for the work I am about to do 2 Do I know why I m doing this work 3 Have I identified and notified all key stakeholders who will be directly and possibly indirectly affected by this work...

Page 4: ...lead change every 24 hours LCD display for current operating mode and shelter temperature readings Comfort mode to allow Occupied settings for a one hour timed duration Five button keypad for navigati...

Page 5: ...be snug and depressing the clips through the slot openings may help in getting the cover off 4 Mount the Plate Dress the wires through the center window on the back plate and install mounting screws T...

Page 6: ...C R C G Y1 W Supply Fan Cooling Heating Control Interface Located in HVAC system HVAC 2 HVAC 2 C R T Stat Lead Lag Controller Back plate mounts to standard electrical box HVAC Unit 2 24VAC R C G Y1 W...

Page 7: ...ewed by pressing the up or down arrow keys This will cycle the display on the second line to show Occupied status and control mode of each HVAC unit 3 2 Occupied Override Press the center button until...

Page 8: ...mode Lag unit cooling on 80 Comfort mode All cooling off 71 Comfort mode Lead unit heating on 55 Comfort mode Lag heating on 53 Comfort mode All heating off 60 Lead Switch time 24 hours Comfort mode t...

Page 9: ...ot correct the problem reset system by removing the T Stat body from the mounting plate Then return the body to the mounting plate while depressing the up arrow center button and down arrow all at the...

Reviews: