QD6000 and QD7000 Systems
17
Power Requirements
provides the power requirements for the QD6000 and QD7000 base system.
QD6000/QD7000 Base System Acoustic Noise Levels
provides the acoustic noise levels for the QD6000 and QD7000 base system.
QD6000/QD7000 Base System Site Wiring and Power
This section provides site wiring and power information for the QD6000 and QD7000 base systems.
Site Wiring
The QD6000 and QD7000 base systems use wide-ranging, redundant power supplies that
automatically accommodate voltages to the AC power source. The power supplies meet standard
voltage requirements for both North American (USA and Canada) operation and worldwide (except
USA and Canada) operation. The power supplies use standard industrial wiring with line-to-neutral or
line-to-line power connections.
Keep this information in mind when you prepare the installation site for the QD6000 and QD7000
base systems:
•
Protective ground – Site wiring must include a protective ground connection to the AC power
source.
Table 15
QD6000 and QD7000 Base System Power Requirements
Component
Typical Operating Power
Rated Power Requirement
QD6000 Base System with HIC (6-TB
drives fully populated
KVA: 1.075
KVA: 1.526
Watts: 1064
Watts: 1512
Btu/Hr: 3632
Btu/Hr: 5159
QD7000 Base System with HIC (6-TB
drives fully populated
KVA: 1.075
KVA: 1.526
Watts: 1064
Watts: 1512
Btu/Hr: 3632
Btu/Hr: 5159
Table 16
QD6000/QD7000 Base System Acoustic Noise Levels
Measurement
Level
Sound power
(standby operation)
7.2 bels
Sound pressure
(normal operation)
7.2 bels
Sound pressure
72 dBA maximum