QD6000 and QD7000 Systems
15
QD6000/QD7000 Base System Altitude Ranges
provides the altitude ranges of the QD6000 and QD7000 base system.
Relative humidity (no
condensation)
Operating range (both cabinet and
subsystem)
20% to 80%
Storage range
10% to 90%
Transit range
5% to 90%
Operating gradient
10°C (50°F) per hour maximum
Storage gradient
15°C (59°F) per hour maximum
Transit gradient
20°C (68°F) per hour maximum
Maximum dew point
26°C (79°F)
Maximum gradient
10% per hour
Note
: If you plan to operate a system at an altitude between 1000 m to 3000 m (3280 ft to 9842 ft) above sea
level, lower the environmental temperature 1.7°C (3.1°F) for every 1000 m (3280 ft) above sea level.
Table 13
QD6000/QD7000 Base System Temperature and Humidity Requirements
Condition
Parameter
Requirement
Table 14
QD6000/QD7000 Base System Altitude Ranges
Environment Altitude
Operating
30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Storage
30.5 m (100 ft) below sea level to 3000 m (9840 ft) above sea level
Transit
30.5 m (100 ft) below sea level to 12,000 m (40,000 ft) above sea level