Quantum|ATL StackLink™ Installation Instructions
Document 6421009-03, Ver. 3, Rel. 0
November 2001
22
Cabling the Library
Terminator Power
0
External terminators must be installed at the end of each SCSI bus.
Power for the terminator must be supplied by at least one device on
the SCSI bus.
In the factory default configuration, the library robotics supplies
terminator power. You can turn this terminator power off using the
Terminator Power
option on the GUI
Configuration
screen.
Power Cabling
0
To connect the library to AC power:
1
Referring to
, select appropriate AC distribution unit(s) for
your library configuration and input voltage.
Table 2 AC Distribution
Unit Requirements, 200V
to 240V
Warning:
AC distribution units (power strips) must be certified
for safety by an agency acceptable to the country of
use. For use in the United States and Canada,
distribution units must be UL listed and CSA
certified. For use in Europe, distribution units must
be CE marked. National certifications for other
countries depend on local requirements.
# of
Library
Modules
Distribution Unit Requirements
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
1-5
Connect libraries to one AC distribution unit
rated minimum 10A, minimum 1.00mm
2
<HAR> cord with minimum 10A plug. Must
be 3 wire grounding plug and wall outlet.
Connect libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG 3 wire cord, and a 15A or
20A plug. Must be 3 wire grounding plug and
wall outlet.