Owner’s Manual
Quantum Energy Technologies
Document number: QDC0030PD-11 Page 26 of 40
10b.1: First Level: Press SET + UP for 6 Seconds
t10
Compressor start time delay; 1 to 30 min adjustable. Factory setting 10 min.
p10
Interval for compressor start after stop; 3 to 30 min adjustable. Factory setting 10 min.
d10
Interval for over heat auto-reset; 3 to 30 min adjustable. Factory setting 10 min.
E10
The max de-icing time; 5 to 30 min adjustable. Factory setting 10 min.
F45
The interval for de-icing; 10 to 99 min adjustable. Factory setting 45 min.
10b.2: Second Level: Press SET+DOWN for 6 Seconds
A65
Highest water temperature setting; 30 to 65
℃
adjustable. Factory setting 65
℃
.
d05
Temperature difference for heat pump reactivation (H55 - d05=50
℃
) 5 to 30
℃
adjustable.
Factory setting 5
℃
.
H95
Overheat trip-out temperature; 60 to 98
℃
adjustable. Factory setting 95
℃
.
L70
Overheat reset temperature; 60 to 98 adjustable. Factory setting 70
℃
.
P85
Liquid Injection activation temperature; 55 to 98
℃
adjustable. Factory setting 85
℃
.
b75
Liquid Injection de activation temperature; 55 to 98
℃
adjustable. Factory setting 75
℃
.
F08
De-ice de activation temperature; 1 to 15
℃
adjustable. Factory setting 8
℃
.
C-5
De-icing temperature setting; -9
℃
to -1
℃
; Factory setting -5
℃
.
10b.3: Third Level: Press UP+DOWN for 6 Seconds
FXX
Start Up model; F00 to F03 adjustable. Factory setting F02.
F00
Following compressor start the Liquid Injection & De Icing valves remain closed.
F01
Following compressor start the Liquid Injection valve opens, 3 seconds later it closes.
F02
Following compressor start the De-Icing valve opens, 3 seconds later it closes.
F03
Following compressor start the Liquid Injection & De Icing valves open, 3 seconds later they
close.
A25
Compressor amperage overload adjustment; 0 to 30 Amps adjustable. Factory setting 25A.
10c: Error Codes
E01
Water temperature sensor open or short circuit. Auto reset.
E02
Compressor temperature sensor open or short circuit. Auto reset.
E03
Evaporator temperature sensor open or short circuit. Auto reset.
E04
Compressor overload protection. Auto reset the first time, manual reset the second time.
E05
Compressor overheat protection (exceeding H95 setting). Auto reset.
E06
Compressor overheat protection (exceeding 105
℃
). Manual reset.
E08
Ambient temperature sensor open or short circuit (Optional). Auto reset.