Owner’s Manual
Quantum Energy Technologies
Document number: QDC0030PD-11 Page 33 of 40
A.
3: No Hot Water; Compressor Running
Probable Cause
Test / Observation
Action
1. Tank water drawn off - unit only
recently started.
Wait until water is heated.
If water is not heated in the expected time,
check for other reasons.
2. Low or no refrigerant.
Check for shortage of refrigerant or leakage in the system.
Refer to Table A.2: Item 1
3. Compressor is not pumping.
a. Check for internal valve leak. When shut off, gas will go
back through the compressor making noise and vibration.
b. Minimum pressure difference across compressor due to TX
valve malfunction. Test TX valve.
a. Replace compressor if faulty.
b. Adjust or Replace TX valve.
4. Frozen evaporator.
a. Malfunction of de-ice system or persistent cold weather
resulting in poor performance of the fin coil evaporator.
b. Blocked evaporator.
c. Restricted airflow.
a. Repair or replace de-ice system or avoid
running in constant cold weather.
b. Repair blockage or replace parts.
c. Clean or replace air filter (if fitted), or
provide ventilation.
A.
4: Shortage Of Hot Water
Probable Cause
Test / Observation
Action
1. System under sized.
Check actual load with design load.
Re-size.
2.
Unexpected load or weather
condition.
a. Check for excessive hot water draw.
b. Check for not water leakage.
c. Check heat loss if the heater is on reticulation circuit.
a.
Re-size if extra hot water draw is to be
included in the design.
b.
Repair leakage if found.
c. Re-size with heat loss included in the
design or install booster.
3. System not producing enough heat. Check according to Table A.3: item 2, 3 & 4.
See Table A.3: items 2, 3 & 4.
Summary of Contents for 270-11AC3-134
Page 29: ......
Page 30: ......
Page 38: ...Owner Manual Quantum Energy Technologies BLANK PAGE Document number QDC0030PD 11 Page 38 of 40...