SECTION 7 - OPERATION
OPERATING CONTROLS
Unit Switch
A double pole single throw ON/OFF rocker switch on
the front of the control panel is used to turn the entire
chiller ON and OFF. When the switch is placed in the
OFF position, the entire unit shuts down immediately
and all systems will be disabled. One pole of the UNIT
switch contacts is wired to the Run Signal input and the
Chiller Control Board “UNIT switch X” digital input
(X equals System 1 or 2). Separate System Fuses are
also wired in series with each set of UNIT switch con-
tacts. If either fuse is pulled or blown, only the system
with the good fuse (Input is high) will run. When both
inputs are high, the entire chiller will be enabled to run.
When both inputs are low, the chiller will be disabled
as a UNIT switch OFF Shutdown.
Keypad
An operator keypad allows complete control of the sys-
tem from a central location. The keypad offers a multi-
tude of command keys on the left and right side of the
keypad to access displays, program setpoints, history
data, and initiate system commands. Most keys have
multiple displays that can be accessed by repetitively
pressing the key or by pressing the ▲,▼,◄, and ►
(ARROW) keys. The keypad utilizes an overlay to
convert the keypad to various languages.
LD21850
UNIT
SWITCH
KEYPAD
DISPLAY
FIGURE 17 -
KEYBOARD AND DISPLAY
The keypad also contains keys in the center section for
data entry in the various program modes. These keys
are listed below:
• 0-9 Keys NUMERIC KEYPAD
• PERIOD/DECIMAL
• +/-
PLUS/MINUS
•
ENTER
•
CANCEL
•
▲ UP ARROW
•
▼ DOWN ARROW
•
◄ LEFT ARROW
•
► RIGHT ARROW
The numeric keys allow keying numeric values into
memory.
The • (PERIOD/DECIMAL) key allows keying a
decimal point into numeric values.
The +/- (PLUS/MINUS) key allows making numeric
values negative.
The
(ENTER) key stores program changes into
memory.
The X (CANCEL) key is used to cancel the data en-
try operation and returns the programmed value to the
original value, before any programming changes were
made, when an error is made.
The ▲ (UP ARROW) and ▼ (DOWN ARROW)
keys allow scrolling backward (▲) and forward (▼)
through items to be programmed under keys such as the
PROGRAM or OPTIONS key.
The ▲ (UP ARROW) and ▼ (DOWN ARROW)
keys also allow scrolling forward (▼) or backwards
(▲) through data display keys that have multiple
displays under keys such as UNIT DATA, SYSTEM
DATA, HISTORY, PROGRAM, OPTIONS, etc. The
arrow keys can be used instead of repeatedly pressing
the data key to see the multiple displays under a key.
Once the ▲ ▼ (ARROW) keys are pressed and used
for scrolling, pressing the original data key will return
to the first display message displayed under the data
(UNIT DATA, SYSTEM DATA, etc.) keys.
Summary of Contents for QTC4 STYLE A Series
Page 22: ...QUANTECH 22 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...QUANTECH 34 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...QUANTECH 56 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 90: ...QUANTECH 90 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 148: ...QUANTECH 148 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 160: ...QUANTECH 160 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 163: ...QUANTECH 163 FORM QTC4 NM1 ISSUE DATE 4 2 2018 NOTES...