SECTION 8 - MICROPANEL
QUANTECH
133
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
8
TABLE 22 -
SETPOINT LIMITS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Leaving Chilled Liquid Setpoint
Water Cooling
40.0°F
60.0°F
44.0°F
4.4°C
15.6°C
6.7°C
Glycol Cooling
15.0°F
70.0°F
44.0°F
-9.4°C
15.6°C
6.7°C
Leaving Chilled Liquid Control Range
-
1.5°F
2.5°F
2.0°F
0.8°C
1.4°C
1.1°C
Max. Remote Temperature Reset
-
2°F
40°F
20°F
1°C
22°C
11°C
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in the
following table.