3.1 Floor Space and Floor Loading
3-12
501604 Rev. 07-01-19
XLS-812300 Floor Space
Table 3-7
lists the amount of floor space required to install the XLS-812300. The aisle
space calculations include an aisle of 24 inches (61 cm) on the front or back of the
equipment..
Number of units
Cabinets only
Cabinets with 24-inch aisle
LRMs
Pods
XL-
85000M
EMs
Sq. feet
Sq.
meters
Sq. feet
Sq. meters
1
0
9
1
14.2
1.3
2
17
1.6
20.6
1.9
1
14
2
18
2
2
20
2
27
3
Table 3-7
Floor space requirements for the XLS-812300 (see
Figure 3-8 on page 3-13
)
XLS-812300 Floor Loading
Table 3-8
shows the weight and maximum floor loading for the XLS-812300, assuming
that expansion pods are installed on both the left and right sides.
Unit
Tape
drives
Cartridges
Net weight
empty
(lbs / kg)
Net weight
loaded (lbs
/ kg)
Floor loading
(lbs/ft
2
/ kg/m
2
)
LRM
4
295
720 / 327
898 / 407
107 / 532
LRM
12
535
720 / 327
1162 / 527
138 / 675
85000 MEM
—
535
420 / 191
687 / 312
127 / 621
Table 3-8
Weight and maximum floor loading for the XLS-812300
Site Planning for Expansion Pods
The XLS-812300 can be expanded by adding one or two expansion pods. If you plan to
install expansion pods (whether during the initial installation or in the future), consider
the recommended installation order:
1.
Install the base unit.
2.
Install the expansion pod on the
right
side of the base.
3.
Install the expansion pod on the
left
side of the base.