Qualitrol 118 Series Instruction Manual Download Page 21

Electronic Temperature Monitor 

E C N - 2 7 6 4 4  

2 0

 

J u l y   7 ,   2 0 1 0  

 

A

PPENDIX 

E

 

 

ModBus Communications

 

If the Model 118 is equipped with the optional RS-485 port, the unit can 
communicate with a ModBus master station. 

The RS-485 port is located on the side of the Model 118 and is provided with a 
plug-in terminal block connector.  The connector is wired as follows: 
 

 
 
 
 
 
 
 
 

When the RS-485 connector is plugged in with terminals 6 & 7 connected, the RS-
232 data function is disabled. 

Terminals 1 & 3 and terminal 2 & 4 can be connected together if a 2-wire RS-485 
data link is desired. 

The data communicated on the RS-485 link is in ModBus RTU format.  The table 
included shows the data and ModBus register addresses used.  Modbus functions 
03, 06 and 16 are supported. 

The ModBus Data Link parameters can either be set using the User Setup 
software or they can be set up by the following procedure using front panel 
switches: 

1.  Hold all three switches depressed until the unit stops cycling thru the readings 

(approximately 10 seconds).  The unit will then be displaying the current baud 
rate: 

  12 = 1200 bits per second 
  24 = 2400 
  48 = 4800 
  96 = 9600 
192 = 19200 

Pressing the AUDIBLE (middle) button will step the display up thru the above 
choices.  Pushing the MAX MEMORY (bottom) button will step the display 
down thru the above choices 

2.  When the desired baud rate is displayed, press the MANUAL FAN (top) 

button, this will show the current parity setting. 

PE for even parity (standard) 
PO for Odd Parity  
P-- for No parity 

3.  When the desired parity is displayed, press the MANUAL FAN (top) button, 

this will show the current stop bit setting.  If parity is even or odd the display 
will show S1 and will not be able to be changed. 

Terminal – TB4 

Function 

+Receive 

-Receive 

+Transmit 

-Transmit 

Shield Ground 

6 & 7 

Jumper together to 

indicate RS485 is active 

Courtesy of NationalSwitchgear.com

Summary of Contents for 118 Series

Page 1: ...Electronic Temperature Monitor for Dry Transformers 118 series Instruction Manual IST 054 1 Courtesy of NationalSwitchgear com...

Page 2: ...QualiTROL 118 Series Electronic Temperature Monitor for Dry Type Transformers Instruction Manual Courtesy of NationalSwitchgear com...

Page 3: ...___________________ 8 Temperature Display 8 Status Lamps 8 Alarm Audible 8 Push Buttons 8 Fan Exerciser 9 Functional Specification __________________________________________________________ 10 Setup S...

Page 4: ...ntervals ON time and interval is programmable Operates a relay with a SPDT contact when one of the inputs exceeds the ALARM setting A RED LED indicates that the ALARM is ON An internal audible device...

Page 5: ...ons to guide you through mounting supplying power to and wiring your Temperature Monitor Operation A description of use during transformer operation as well as easy instructions on how to perform a sy...

Page 6: ...nitor The 118 mounts in a rectangular cutout in a panel and is secured by four 4 bolts See Figure 1 118 Dimensions Figure 1 118 Dimensions The 118H mounts in a rectangular cutout in a panel and is sec...

Page 7: ...the internal temperature of the ETM If the channel is not used it can be turned OFF using the setup software but the terminals still need to be shorted together Relay Contacts FAN 1 The 1 fan contacts...

Page 8: ...p Software section of this manual for more detailed information NOTE Wires should be connected to the RS 232 terminals only during parameter setup No permanent field wires should be connected to these...

Page 9: ...e of the unit This provides a method of communicating with a remote master station using Modbus RTU protocol Refer to Appendix E of this manual for additional information See Figure 4 RS 485 Wiring Di...

Page 10: ...larm An internal Buzzer sounds each time the ALARM becomes active The buzzer can be silenced by pressing the SILENCE push button The buzzer will then turn OFF and remain OFF until a new ALARM occurs P...

Page 11: ...r The unit has a built in Fan Exerciser function that can turn the fans on for a short period of time at periodic intervals The default setting is for 1 minute every 7 days The Fan Exerciser can be co...

Page 12: ...500 max load Accuracy 1 of full scale reading Fan Exerciser Fan Run Time 1 to 120 minutes Fan Cycle Time 0 01 to 30 0 days Time starts at power up Environment Operating Temperature 30 C to 72 C Stora...

Page 13: ...are consists of these menu selections Installation Run SETUP BAT on the installation CD This will create a directory C QualiTROL on the hard drive and will install the program and default configuratio...

Page 14: ...to be detected quickly If the thermocouple is connected incorrectly as the temperature goes up the display temperature goes down If the reverse thermocouple feature is activated when the thermocouple...

Page 15: ...dual fuses Remote Output 0 0 1mA loop 4 4 20mA loop Thermocouple K Type K Voltage 120 120VAC 240 230 240VAC 277 277VAC Package P Panel mounting plate H Box with hinged front cover FAN turns ON at ____...

Page 16: ...to step the Alarm setpoint up or down Push the MANUAL FAN button The TRIP light will be on and the display will show the Trip setpoint Use the AUDIBLE and MAX MEMORY buttons to step the Trip setpoint...

Page 17: ...he fans turn ON If the unit is installed in an enclosure no further protection is required If the unit is mounted without being installed in an enclosure then to maintain the rated accuracy some form...

Page 18: ...Electronic Temperature Monitor ECN 27644 17 July 7 2010 THERMOCOUPLE WIRE COPPER WIRE Model 118 ETM Millivolt Source ICE BATH Courtesy of NationalSwitchgear com...

Page 19: ...lay Driver Continue to operate Failed Microprocessor Unit will not operate but failure is detected The FANS will turn ON and ALARM relay will be in the alarm state Intermittent sensor connection If th...

Page 20: ...unit and within easy reach of the operator It shall be marked as the disconnecting device for the equipment Radio Frequency interference above Level 1 of EN 61000 4 6 conducted on the Mains wiring ma...

Page 21: ...or they can be set up by the following procedure using front panel switches 1 Hold all three switches depressed until the unit stops cycling thru the readings approximately 10 seconds The unit will t...

Page 22: ...hed for 30 seconds the unit will automatically return to normal operation with the communications setup unchanged Modbus Reg No Data Returned when Register Is addressed Comments 40001 40002 40003 Temp...

Page 23: ...is disabled 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 Fan setpoint Alarm setpoint Trip setpoint Fan Switching differential hysteresis Alarm Switching differential hysteresis Trip Sw...

Reviews: