background image

August 3, 2015   

 

 

              

7075-209E 

 

 

 

         

                  25

VOYAGEUR GRAND

Figure 25.1 

 

Spark Arestor Cap 

Roof Flashing 

Storm Colla

Joist Shield/Firestop 

Double Wall 
Connector Pipe  

8.  Burn wood only.  Other types of fuels may generate 

poisonous gases (e.g., carbon monoxide).

9. 

If unit burns poorly while an exhaust blower is on in home, 
(i.e., range hood), increase combustion air.

10.  Installation shall be in accordance with the Manufacturers 

Home & Safety Standard (HUD) CFR 3280, Part 24.

NOTICE: 

•  

Offsets from the vertical, not exceeding 45°, are allowed 

per Section 905(a) of the Uniform Mechanical Code (UMC). 

•  

Offsets greater than 45° are considered horizontal and are 

also allowed, providing the horizontal run does not exceed 
75% of the vertical height of the vent. 

•  

Construction, clearance and termination must be in com-

pliance with the UMC Table 9C. This installation must also 
comply with NFPA 211.

NOTICE:

 Top sections of chimney must be removable to allow 

maximum clearance of 13.5 feet (411cm) from ground level 
for transportation purposes.

1. 

An outside air inlet must be provided for combustion and 
must remain clear of leaves, debris, ice and/or snow.  It 
must be unrestricted while unit is in use to prevent room 
air starvation which can cause smoke spillage and an 
inability to maintain a fi re.  Smoke spillage can also set 
off smoke alarms.

2. 

Unit must be secured to the mobile home structure at 
two attachment points.   Remove bolts from each side 
of insert and use plumbers tape to secure to structure 
(a washer may be required). Re-install bolts.  

3. 

Unit must be grounded with #8 solid copper grounding 
wire or equivalent and terminated at each end with N.E.C. 
approved grounding device.

4.  The factory-built fireplace must meet (UM)84-HUD 

requirements for outside combustion air supply to 
the  fi replace  fi re chamber and the chimney must be 
listed to UL103 HT or a listed UL-1777 full length six 
inch (152mm) diameter liner must be used. It must be 
equipped with a spark arrestor cap and the outside air 
must be installed on the insert. 

5. Refer 

to 

pages 7-8

 of this manual for clearance to 

combustibles and fl oor protections requirements.

 

 All 

clearances must be followed precisely.

6.  Use silicone to create an effective vapor barrier at 

the location were the chimney or other component 
penetrates to the exterior of the structure.

7. 

Follow the chimney and chimney connector manufacturer’s 
instructions when installing the fl ue system for use in a 
mobile home.

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 
FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED

Do NOT cut through:
•  Floor joist, wall, studs or ceiling trusses.

• 

Any supporting material that would affect the structural 

     integrity.

• 

NEVER INSTALL IN A SLEEPING ROOM.

Consumes oxygen in the room.

WARNING

Asphyxiation Risk.

WARNING

Do not draw outside combustion air from:
• Wall, 

fl oor or ceiling cavity

•  Enclosed space such as an attic or garage

•  Close proximity to exhaust vents or chimneys.

Fumes or odor may result

Fire Risk.

Asphyxiation Risk.

Mobile Home Installation

Summary of Contents for VOYA-GRAND-MBK

Page 1: ...any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure...

Page 2: ...Needed 6 E Inspect Appliance and Components 6 F Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearances to Combustibles 9 C Locating Your Stove Chimney 11 D Chimney Termi...

Page 3: ...om and when an outside combustion air inlet is provided The structural integrity of the mobile home floor ceil ing and walls must be maintained The appliance must be properly grounded to the frame of...

Page 4: ...Tile Glass Slate Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace of 750 C F Combustible Materials Material made of or surfaced with any...

Page 5: ...and national codes and regulations Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits CAUTION WARNING DO...

Page 6: ...d air handler joints and seams taped or sealed Basement installations should be avoided D Tools And Supplies Needed Before beginning the installation be sure the following tools and building supplies...

Page 7: ...he minimum height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 8 Combustible materials not installed in non combustible areas Verified all...

Page 8: ...79mm 4 102mm 2 7 8 73mm 23 1 2 597mm 6 1 16 154mm Surround Sizes A B Standard 43 in 1092mm 33 in 787mm Large 51 in 1346mm 34 in 864mm Applies to surround with cast trim only 14 356mm 25 3 4 655mm 25 1...

Page 9: ...n USA a minimum 5 ft length 1 82m 6 inch 152mm diameter flue liner is required as per UL 1482 32 5 8 829mm 22 1 2 572mm 43 1092 mm USA 38 1 4 CANADA 46 1 4 1175mm HEARTH EXTENSION MINIMUM EMBER PROTEC...

Page 10: ...t2 hour o F Thermal Resistance R value The R value is a measure of a material s resistance to heat transfer R value is convenient when more than one material is used since you can add the R values tog...

Page 11: ...tall through the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roof This minimiz...

Page 12: ...m Minimum 3 ft 91cm Minimum Wall or Parapet E 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimney connec...

Page 13: ...for cleaning and re installation When possible install an airtight clean out door to the rear of the smoke shelf A Venting Systems Chimney Connector It is also known as flue pipe or stove pipe It must...

Page 14: ...Accordance with Insert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Offset in Chimney Combustible Floor Masonry Chimney Cont d This insert co...

Page 15: ...flue collar and the chimney top The air flow of the factory built zero clearance fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existi...

Page 16: ...replace opening the portion of the insert extending onto the hearth must be supported Manufacturer designed adjustable support kit can be ordered from your dealer Final approval of this installation t...

Page 17: ...ding 25 feet 7 62m from base of appliance may create an over draft situation Overdraft condition may create over firing Over firing may ignite creosote and or damage appliance and chimney WARNING I Ze...

Page 18: ...ir supply duct shall NOT exceed the length of the vertical height of the exhaust flue Fire will not burn properly Smoke spillage occurs when door is opened due to air starvation WARNING Option One Out...

Page 19: ...Duravent 15 Universal Elbow Part Number 4615 may be purchased directly through your local Simpson Durvent Pipe Distributor or from your local Quadra Fire dealer Part Number DV 6DLR E15ADSS Figure 19...

Page 20: ...ight 3 Re install the screws to secure in place E Securing Appliance to Stove Pipe Liner 1 Once you have the appliance in place and secured reach up through the flue opening and grab the attachment ba...

Page 21: ...cast footers under the metal sides aligning the top and bottom holes in the cast footers and metal sides 8 The 9 mounting clips are shipped in one long strip Hand break apart or use pliers 9 Each clip...

Page 22: ...on a protected surface to prevent scratching 3 Align the bosses on the top piece to the holes on the side pieces Secure the 3 pieces together 4 Attach the mounting brackets to the side pieces include...

Page 23: ...from appliance and store away from your work area 2 Remove the 2 screws in the hold down bracket in front of the blower assembly You do not need to remove the blower from the hold down bracket 3 Disc...

Page 24: ...late White Wire Black Wire Fiber Wrapped Wire Green Grounding Wire 11 Connect the white wire on the power cord into the fiber wrapped wire on the wire harness Connect the black wire on the power cord...

Page 25: ...lts from each side of insert and use plumbers tape to secure to structure a washer may be required Re install bolts 3 Unit must be grounded with 8 solid copper grounding wire or equivalent and termina...

Page 26: ...g 1 4 20 x 3 4 Pkg of 25 228 0120 25 Y Washer Bonded 5 16 x 3 4 Pkg of 10 229 0910 10 Y 14 2 Hinge Continous 7000 510 Screw Flat Head Phillips 8 32 x 1 2 Pkg of 12 220 0490 12 Y 14 3 Access Matte Blac...

Page 27: ...ervice parts from your dealer or distributor Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 25 Surrounds Cast Matte Black SP GRAND CC MBK Porcelain Mahogany SP GRAND CC PMH 25 1 Surround Right...

Page 28: ...GRAND CM LRG 26 1 Trim Leg Right Matte Black 414 7130MBK Porcelain Mahogany 414 7130PMH 26 2 Trim Header Matte Black 414 7110MBK Porcelain Mahogany 414 7110PMH 26 3 Trim Leg Left Matte Black 414 7120M...

Page 29: ...August 3 2015 7075 209E 29 VOYAGEUR GRAND...

Page 30: ...30 7075 209E August 3 2015 VOYAGEUR GRAND...

Page 31: ...August 3 2015 7075 209E 31 VOYAGEUR GRAND...

Page 32: ...mportant operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instruc tions for safe installa tion and opera...

Reviews: