VOYAGEUR GRAND

Inches

Millimeters

Minimum Width of Cavity Opening - Front

32-7/8

835

Minimum Width of Cavity Opening - Rear

24

610

Minimum Height

24

610

Minimum Depth from Front to Rear

18

457

Damper

Smoke Shelf or Baffl e

Ember Catches

Fire Grate

Viewing Screen/Curtain

Doors

The following parts may be removed:

The following modifi cations of factory-built fi replaces  are 
permissible:

• 

The fi replace must not be altered. Cutting any sheet metal 
parts of the fi replace in which the fi replace insert is to be 
installed is prohibited per ANSI Z21.88 except that the 
damper may be removed to accommodate a direct-connect 
starter pipe or chimney liner,

• E

xternal trim pieces which do not affect the operation of 

the fi replace may be removed providing they can be stored 
on or within the fi replace for reassembly if the insert is 
removed.

• 

The permanent metal warning label provided in the 
component pack must be attached to the back of the 
fi replace, with screws or nails, stating that the fi replace may 
have been altered to accommodate the insert, and must 
be returned to original condition for use as a conventional 
fi replace.

• 

If the hearth extension is lower than the fi replace opening, 
the portion of the insert extending onto the hearth must be 
supported.

 

•  

Manufacturer designed adjustable support kit can be 
ordered from your dealer.  

• 

Final approval of this installation type is contingent upon 
the authority having jurisdiction.

Fire Risk.

When lining air-cooled factory-built chimneys:.

•  Run chimney liner approved to UL 1777 Type 

HT requirements (2100 degrees F)

•  Re-install original factory built chimney cap 

ONLY

•  DO NOT block cooling air openings in chimney

•  Blocking cooling air will overheat the chimney

WARNING

Prefabricated Metal Chimney (Cont’d)

LINER CONNECTOR

FLUE

 GAS 

DIRECTION

CRIMPED 

END 

TOWARDS 

STOVE

Figure 16.1

NOTICE: In Canada when using a factory-built chim-
ney it must be safety listed, Type UL103 HT (2100oF) 
[1149oC] CLASS “A” or conforming to CAN/ULC-
S629M, STANDARD FOR 650oC FACTORY-BUILT 
CHIMNEYS.

NOTE:  Refer to chimney liner manufacturer for recom-
mendations on supporting the liner.  Installation into 
fi replaces without a permit will void the listing.

H.  Altering the Fireplace

G.  Securing Chimney Components

All joints should be secured with 3 sheet metal screws or 
rivets per pipe manufacturers instructions. The sections must 
be attached to the insert and to each other with the crimped 
(male) end pointing toward the insert.  

Figure 15.1

.

WARNING! Risk of Fire!

Follow venting manufacturer’s clearances and instructions 
when installing venting system.

Summary of Contents for VOYA-GRAND-MBK

Page 1: ...any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure...

Page 2: ...Needed 6 E Inspect Appliance and Components 6 F Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearances to Combustibles 9 C Locating Your Stove Chimney 11 D Chimney Termi...

Page 3: ...om and when an outside combustion air inlet is provided The structural integrity of the mobile home floor ceil ing and walls must be maintained The appliance must be properly grounded to the frame of...

Page 4: ...Tile Glass Slate Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace of 750 C F Combustible Materials Material made of or surfaced with any...

Page 5: ...and national codes and regulations Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits CAUTION WARNING DO...

Page 6: ...d air handler joints and seams taped or sealed Basement installations should be avoided D Tools And Supplies Needed Before beginning the installation be sure the following tools and building supplies...

Page 7: ...he minimum height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 8 Combustible materials not installed in non combustible areas Verified all...

Page 8: ...79mm 4 102mm 2 7 8 73mm 23 1 2 597mm 6 1 16 154mm Surround Sizes A B Standard 43 in 1092mm 33 in 787mm Large 51 in 1346mm 34 in 864mm Applies to surround with cast trim only 14 356mm 25 3 4 655mm 25 1...

Page 9: ...n USA a minimum 5 ft length 1 82m 6 inch 152mm diameter flue liner is required as per UL 1482 32 5 8 829mm 22 1 2 572mm 43 1092 mm USA 38 1 4 CANADA 46 1 4 1175mm HEARTH EXTENSION MINIMUM EMBER PROTEC...

Page 10: ...t2 hour o F Thermal Resistance R value The R value is a measure of a material s resistance to heat transfer R value is convenient when more than one material is used since you can add the R values tog...

Page 11: ...tall through the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roof This minimiz...

Page 12: ...m Minimum 3 ft 91cm Minimum Wall or Parapet E 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimney connec...

Page 13: ...for cleaning and re installation When possible install an airtight clean out door to the rear of the smoke shelf A Venting Systems Chimney Connector It is also known as flue pipe or stove pipe It must...

Page 14: ...Accordance with Insert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Offset in Chimney Combustible Floor Masonry Chimney Cont d This insert co...

Page 15: ...flue collar and the chimney top The air flow of the factory built zero clearance fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existi...

Page 16: ...replace opening the portion of the insert extending onto the hearth must be supported Manufacturer designed adjustable support kit can be ordered from your dealer Final approval of this installation t...

Page 17: ...ding 25 feet 7 62m from base of appliance may create an over draft situation Overdraft condition may create over firing Over firing may ignite creosote and or damage appliance and chimney WARNING I Ze...

Page 18: ...ir supply duct shall NOT exceed the length of the vertical height of the exhaust flue Fire will not burn properly Smoke spillage occurs when door is opened due to air starvation WARNING Option One Out...

Page 19: ...Duravent 15 Universal Elbow Part Number 4615 may be purchased directly through your local Simpson Durvent Pipe Distributor or from your local Quadra Fire dealer Part Number DV 6DLR E15ADSS Figure 19...

Page 20: ...ight 3 Re install the screws to secure in place E Securing Appliance to Stove Pipe Liner 1 Once you have the appliance in place and secured reach up through the flue opening and grab the attachment ba...

Page 21: ...cast footers under the metal sides aligning the top and bottom holes in the cast footers and metal sides 8 The 9 mounting clips are shipped in one long strip Hand break apart or use pliers 9 Each clip...

Page 22: ...on a protected surface to prevent scratching 3 Align the bosses on the top piece to the holes on the side pieces Secure the 3 pieces together 4 Attach the mounting brackets to the side pieces include...

Page 23: ...from appliance and store away from your work area 2 Remove the 2 screws in the hold down bracket in front of the blower assembly You do not need to remove the blower from the hold down bracket 3 Disc...

Page 24: ...late White Wire Black Wire Fiber Wrapped Wire Green Grounding Wire 11 Connect the white wire on the power cord into the fiber wrapped wire on the wire harness Connect the black wire on the power cord...

Page 25: ...lts from each side of insert and use plumbers tape to secure to structure a washer may be required Re install bolts 3 Unit must be grounded with 8 solid copper grounding wire or equivalent and termina...

Page 26: ...g 1 4 20 x 3 4 Pkg of 25 228 0120 25 Y Washer Bonded 5 16 x 3 4 Pkg of 10 229 0910 10 Y 14 2 Hinge Continous 7000 510 Screw Flat Head Phillips 8 32 x 1 2 Pkg of 12 220 0490 12 Y 14 3 Access Matte Blac...

Page 27: ...ervice parts from your dealer or distributor Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 25 Surrounds Cast Matte Black SP GRAND CC MBK Porcelain Mahogany SP GRAND CC PMH 25 1 Surround Right...

Page 28: ...GRAND CM LRG 26 1 Trim Leg Right Matte Black 414 7130MBK Porcelain Mahogany 414 7130PMH 26 2 Trim Header Matte Black 414 7110MBK Porcelain Mahogany 414 7110PMH 26 3 Trim Leg Left Matte Black 414 7120M...

Page 29: ...August 3 2015 7075 209E 29 VOYAGEUR GRAND...

Page 30: ...30 7075 209E August 3 2015 VOYAGEUR GRAND...

Page 31: ...August 3 2015 7075 209E 31 VOYAGEUR GRAND...

Page 32: ...mportant operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instruc tions for safe installa tion and opera...

Reviews: