background image

16

September 27, 2018

7082-153D

TREKKER INSERT

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent 

size 

(Figure 16.1)

.

F. Equivalent Feet of Pipe

Vent surfaces get HOT, can cause burns 

if touched. Non-combustible shielding or 

guards may be required.

WARNING

Example of 3 Elbow-Rear Vent Termination Calculation

Figure 16.1

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Pellet 

Venting 

Component

# of 

Elbows

Feet 

of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components

Equivalent 

Feet

90° Elbow or 

Tee

3

X

5

15

45° Elbow

X

3

Horizontal 

Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

NOTE:

 This is a generic example and is not intended to represent any specific 

fuel type.

Figure 16.2

3 in. or 4 in. (76mm or 102mm) Diameter  Pipe 

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET 

20 

30 

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only 

10 

Example 1

Example 2

Example 1:

 If the equivalent length of pipe is 23 feet (7m) 

with altitude of 8,000 feet (2438m) you must use 

4 inch (102mm) diameter type “L” or “PL” vent.

Example 2:

 If the equivalent length of pipe is 12 feet (3.7m) 

with altitude of 6,000 feet (1829m) you may use 3 

or 4 inch (76 to 102mm) diameter type “L” or “PL” 

vent.

G. Pipe Selection Chart 

The chart will help you in determining proper venting 

size according to the equivalent feet of pipe calculated 

previously and the altitude above sea level of this 

installation (

Figure 16.2).

1. 

Locate the calculated equivalent feet of pipe on the 

vertical left side of the chart.

2.  Move to the right horizontally on the chart until you 

reach your altitude above sea level.

3. 

If you fall below the diagonal line, 3 or 4 inch (76 to 

102mm) pipe may be used.

4.  If it is anywhere above the diagonal line, a 4 inch 

(102mm) diameter pipe is required.

• 

A 90° elbow is 5 times as restrictive to the flow of 

exhaust gases under positive pressure as 1 foot 

(305mm) of horizontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a 

foot of vertical pipe.

NOTICE

Risk of Injury or Property Damage.

•  Improper installation, adjustment, alteration, 

service or maintenance can cause injury or 

property damage.

• 

Refer to the owner’s information manual 

provided with this appliance.

• 

For assistance or additional information 

consult a qualified installer, service agency 

or your dealer.

WARNING

Risk of Fire!

• 

Only LISTED venting components may be 

used.

• 

NO OTHER vent components may be 

used.

•  Substitute or damaged vent components 

may impair safe operation.

WARNING

Summary of Contents for TREKKERI-MBKTREKKERI-CSBTREKKERI-PMH

Page 1: ...s not followed exactly a fire could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appl...

Page 2: ...and Exhaust Connection 15 F Equivalent Feet of Pipe 16 G Pipe Selection Chart 16 5 Venting Systems 17 A Full Reline wit Outside Air Horizontal 17 B Full Reline with Outside Air Vertical 18 6 Applianc...

Page 3: ...0061PS094E EPA Certification 98 17 EPA Certified Emissions 0 74 g hr LHV Tested Efficiency 83 2 HHV Tested Efficiency 77 9 EPA BTU Output 12 682 39 428 HR BTU Input 16 396 50 775 HR Vent Size 3 4 or...

Page 4: ...ects or other reproductive harm For more information go to WWW P65Warnings ca gov G Combustible Materials Material made of or surfaced with any of the following materials Wood Compressed Paper Plant F...

Page 5: ...cient additional support to meet this weight requirement prior to installation The weight of the appliance is 510 lbs with a full load of fuel the max weight is 557 lbs NOTICE Check building codes pri...

Page 6: ...onsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home...

Page 7: ...ion and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the app...

Page 8: ...5mm 26 7 8 in 683mm 11 7 8 in 302mm 24 1 8 in 613mm 33 in 838mm 50 in 1270mm 34 1 2 in 876mm 45 in 1143mm 11 3 4 in 297mm 18 1 2 in 469mm Figure 8 2 Front View with Cast Panel Set 23 7 8 in 606mm 32 i...

Page 9: ...or choice must be added to this dimension Figure 9 1 Built in Appliance Rear Vent NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn...

Page 10: ...required Ember protection only If mantel depth is 10 inches or less than the height from the hearth to the bottom of the mantel is 39 3 4 inches Minimum Opening Dimensions Inches Millimeters A Height...

Page 11: ...ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Heath Home Technologies 250 2061 5 5 in width x 2 in height NON AN...

Page 12: ...ll height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and the chimney top The air flow of the...

Page 13: ...es and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in t...

Page 14: ...he demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation...

Page 15: ...hrough the chimney Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successfu...

Page 16: ...00 feet 1829m you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe...

Page 17: ...ombustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of NFPA 211 F...

Page 18: ...12 in 305mm min below 12 in 305mm min below NOTE In Canada this fireplace insert must be installed with a continuous chimney liner extending from the fireplace insert to the top of the chimney The ch...

Page 19: ...veling bolts if necessary to keep the insert level when installing Figure 19 3 Bend tabs down Shipped flat from the factory Included in Kit 1 bottom 1 trim front 2 trim sides 2 trim extensions Tools N...

Page 20: ...owered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim pieces 2 Lay the surround set face down on protective covering to prevent scratching t...

Page 21: ...21 3 Back of Top Surround Back of Side Surround Screws Figure 21 1 Shown with trim installed on panel set 2 PIECE LOG SET INSTALLATION 1 Place the left log as shown There are 2 indentations in the bot...

Page 22: ...Key J Location Mounting of User Interface Shock hazard Do NOT remove grounding prong from plug Plug directly into properly grounded 3 prong receptacle Route cord away from appliance Do NOT route cord...

Page 23: ...art Number OAK 3 Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 23 1 WARNING Products of combustion generate carbon monoxide and differen...

Page 24: ...24 September 27 2018 7082 153D TREKKER INSERT Date of Service Performed By Description of Service 8 Reference Materials A Service Maintenance Log...

Page 25: ...25 September 27 2018 7082 153D TREKKER INSERT Date of Service Performed By Description of Service...

Page 26: ...26 September 27 2018 7082 153D TREKKER INSERT Date of Service Performed By Description of Service...

Page 27: ...Y Outside Air Kit OAK 3 Top Vent Adapter TPVNT 4 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim SP MTVS GD Component Pack 7036 042 Trim Panel Set G...

Page 28: ...te purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ De...

Reviews: