background image

 14 

 

 

 

 

                          7019-230C 

 

 

 

                 May 18, 2015

Santa Fe Pellet Insert

C.  Negative Pressure

Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be strongest 
in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

• Range 

hoods

•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

• Clothes 

dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 - 

Recessed 

lighting

 - 

Attic 

hatch

 - 

Duct 

leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

• 

Ensure adequate outdoor air for all combustion appliances 
and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

• 

Attic mounted duct work and air handler joints and seams 
taped or sealed

D.  Draft 

Draft is the pressure difference needed to vent an appli-
ance successfully. When an appliance is drafting suc-
cessfully, all combustion byproducts are exiting the home 
through the chimney.

Install through the warm airspace enclosed by the build-
ing envelope. This helps to produce more draft, especially 
during lighting and die-down of the fi re.

Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney

NOTICE:  Hearth & Home Technologies assumes no 
responsibility for the improper performance of the chimney 
system caused by:

•  Inadequate draft due to environmental conditions
• Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

E.  Chimney and Exhaust Connection 

1.

 

Chimney & Connector

:  Use 3 or 4 inch (76-102mm)  diameter 

type “L” or “PL” venting system.  It can be vented vertically or 
horizontally.

2.

 Mobile Home: 

Approved for all Listed pellet vent.  If using the 

3 inch (76mm) vertical Top Vent Adapter Kit or the 3 to 6 inch 
(76-152mm) Top Vent Offset Adapter, use Listed double wall 
fl ue connector.  A Quadra-Fire Outside Air Kit must be used with 
manufactured home installations.

3.

 Residential: 

 The 3 inch (76mm) vertical Top Vent Adapter Kit and 

the 3 to 6 inch (76-152mm) Top Vent Offset Adapter are tested 
to use 24 gauge single wall fl ue connector or Listed double wall 
fl ue connector to Class A Listed metal chimneys, or masonry 
chimneys meeting International Residential Code standards for 
solid fuel appliances.

4.

  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 

VENT MANUFACTURER.

5

.  Secure exhaust venting system to the appliance with at least 

3 screws.  Also secure all connector pipe joints with at least 3 
screws through each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENT-

ING SYSTEM OF THIS UNIT.

7.  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 

ANOTHER APPLIANCE.

NOTE:  All pipe must be welded seam pipe whenever possible.  
Seal pipe joints with high temperature silicone (500°F [260°C] 
minimum rated only).

NOTE:  If burning shelled fi eld corn, you must use approved 
venting specifi cally designed for corn.  Follow the instructions 
from the venting manufacturer.

WARNING

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 
fumes and soot.

Summary of Contents for SANTAFEI-MBK

Page 1: ...c tions is not followed exactly a fire could result causing property damage personal injury or death Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to c...

Page 2: ...sions and Clearances 7 A Appliance Dimensions 7 B Clearance To Combustibles UL and ULC 8 C Masonry and Zero Clearance Fireplaces 9 D Minimum Opening for Masonry and Zero Clearance Fireplaces 9 E Hearth Extension 9 F Floor Protection 9 G Installation into a Factory Built Fireplace 10 H Installation into a Masonry Fireplace 11 I Prefabricated Metal Chimney 11 4 Vent Information 11 A Venting Terminat...

Page 3: ...f this appliance reserves the right to alter its products their specifications and or price without notice Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified installer service agency or your dealer Quadra Fire is a registered trademark of Hearth Home Technologies Installation and use of...

Page 4: ...ppliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney offsets Place the appliance where there will be a clear passage for a Listed chimney through the ceiling and roof vertical or through exterior wall horizontal Installing the required outside air kit will affect...

Page 5: ...Thermostat Wall Control Location The thermostat wall control s location will have some affect on the appliance s operation Maximum wire length from appliance is 100 feet 30 48m continuous unspliced wire Recommended 20 gauge wire solid copper When located close to the appliance it may require a slightly higher temperature setting to keep the rest of the house comfortable When located in an adjacent...

Page 6: ...inimum height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 7 Combustible materials not installed in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hearth extension installed per manual requirements A...

Page 7: ...7 1 Top View Figure 7 2 Side View 21 1 2 546mm 28 7 8 733mm 23 5 8 600mm 8 203mm C L 12 3 4 324mm 8 5 8 219mm 23 584mm 25 3 8 645mm Panel A B Standard 40 inches 1016mm 30 inches 762mm Large 50 inches 1270mm 33 inches 838mm A B 3 Dimensions and Clearances A Appliance Dimensions ...

Page 8: ... D C B 0 in Clearance To Exposed Section And Face Trim C L B Clearance To Combustibles UL and ULC Inches Millimeters A Top of Hopper Top Vent 2 0 51 Rear Vent 2 5 64 B Side of Hopper Top or Rear Vent 2 0 51 C Back of Hopper Top or Rear Vent 2 5 64 D Vent Pipe to Combustible Top or Rear Vent 3 0 76 12 in 305mm Combustible Mantel 6 in 152mm Outside Air Top Vent 2 in 51mm Rear Vent 2 5 in 64mm Back o...

Page 9: ... Depth 16 406 C Height 23 1 4 591 D Front Width 29 1 4 743 Figure 9 1 C Masonry and Zero Clearance Fireplaces Inches Millimeters E Floor protection hearth extension from door opening 6 152 F Floor protection to the side of door opening 6 152 F Floor Protection Figure 9 2 Side Wall Mantel Maximum Mantel Depth 12 inches 305mm Face Trim E F A D C B NOTE It is necessary to permanently seal any opening...

Page 10: ...t the insert The 2 x 4 may need to be cut to the appro priate size 250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Figure 10 1 If the hearth extension is lower than the fireplace opening the portion of the insert extending onto the hearth must be supported Manufacturer...

Page 11: ...oved chimney liner meeting type UL 103 HT requirements 2100 F per UL 1777 If the chimney is not listed as meeting HT requirements or if the factory built fireplace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and the chimney top The air flow of the factor...

Page 12: ...ces and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants wood or any other com bustible 12 in 36 in no OAK Clearance from any forced air intake of other appli ance 12 in Clearance horizontally from combustible wal...

Page 13: ... wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply most of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consu...

Page 14: ...d chimney NOTICE Hearth Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Downdrafts Tight sealing construction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented verti...

Page 15: ...tible shielding or guards may be required WARNING Figure 14 2 3 in or 4 in 76mm or 102mm Diameter Pipe Equivalent Pipe Length In Feet ALTITUDE IN THOUSANDS OF FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 102mm Diameter Pipe Only 10 Example 1 Example 2 Example 1 If the equivalent length of pipe is 23 feet 7m with altitude of 8 000 feet 2438m you must use 4 inch 102mm diameter type L or PL vent Example 2 ...

Page 16: ...ir from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Outside Air through Rear Wall Horizontal NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable ins...

Page 17: ...e 16 2 NOTE In Canada only a full reline is allowed per ULC S628 93 ORD ULC C1482 M1990 NOTE In Canada this fireplace insert must be installed with a continuous chimney liner extending from the fire place insert to the top of the chimney The chimney liner must conform to the Class 3 requirements of CAN ULC S635 Standard for Lining Systems for Existing Masonry or Factory Built Chimneys and Vents or...

Page 18: ...e distance from floor to air vent opening in appli ance and mark location on wall 2 Use saw to cut opening in wall Cut a 2 1 2 to 3 inch 64 76mm opening on inside wall and a 3 to 3 1 2 inch 76 89mm opening on outside of house 3 Use hose clamp to secure flex pipe to collar assembly 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach hose to outside termination cap with second hose c...

Page 19: ...led on the appliance they are then finger bent into position 4 Attach the 4 grille bracket covers to the lower 4 grilles and the top 3 grilles Slip the metal strips through the grille openings and secure to grille with screws provided Do not finger bend the cover brackets at this time 5 Secure the lower grille to the appliance with 2 screws on each side Finger bend the bracket covers around the pl...

Page 20: ...ifficult once trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first and then front piece The front piece overlaps side pieces 7 Once you are satisfied with the positioning remove trim and set aside 8 Remove the paper from double sided tape that is to accept trim side Align side an...

Page 21: ... access panel there are 2 hooks that slip into a slot at the bottom of the side panel and a magnet at the top that holds the access panel in place Figure 20 3 Attach panel legs to top Back view of panel Access Panel Side Panel H Thermostat Installation 1 A 12 volt AC thermostat is required to operate this pellet appliance You may use the included wall mount thermo stat or purchase an optional prog...

Page 22: ... to maintain the desired tem perature in your home 3 There is a 4 screw terminal block located on the junction box to the right of the power cord inlet The center 2 screws are for the thermostat wires The outer 2 are the mounting screws for the terminal block Figure 21 1 Figure 21 1 Figure 21 2 I Optional Log Set Placement Two Piece Log Set Installation 1 Open door to expose the firebox 2 Install ...

Page 23: ...d HUD CFR 3280 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 22 1 CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED Do NOT cut th...

Page 24: ... Plate Outside Air Kit 412 7100 Panel Set Large Black Nickel SP SFI3350 NB No longer available SP SFI3350 GD Nickel SP SFI3350 NL Bracket L Trim 832 0840 Logo Quadra Fire Pkg of 10 7000 649 10 Trim Panel Set Black Nickel 7019 027 Gold 250 4660 Panel Set Small Black Nickel SP SFI3040 NB No longer available SP SFI3040 GD Nickel SP SFI3040 NL Bracket L Trim 832 0840 Logo Quadra Fire Nickel 7000 649 1...

Page 25: ...May 18 2015 7019 230C 25 Santa Fe Pellet Insert ...

Page 26: ...26 7019 230C May 18 2015 Santa Fe Pellet Insert ...

Page 27: ...May 18 2015 7019 230C 27 Santa Fe Pellet Insert ...

Page 28: ...ville WA 99114 Division of HNI INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record the following pert...

Reviews: