B. Full Reline With Outside Air - Vertical
Figure 18.3
NOTE:
Check clearances carefully for this type of
installation to ensure adequate room for outside
air venting.
Direct Connect
45 degree elbow
Side view of Santa Fe Insert with side panel removed
.
Figure 18.1
Figure 18.2
NOTE:
In Canada, only a full reline is allowed per ULC
S628-93, ORD ULC C1482-M1990.
NOTE:
In Canada this fireplace insert must be installed
with a continuous chimney liner extending from
the fireplace insert to the top of the chimney.
The chimney liner must conform to the Class 3
requirements of CAN/ULC-S635, Standard for
Lining Systems for Existing Masonry or Factory-
Built Chimneys and Vents, or CAN/ULC-S640,
Standard for Lining Systems for New Masonry
Chimneys.
Outside Air
Termination
at
Chimney Top
12” (305mm)
min. below
12” (305mm)
min. above
NOTE; Use metal
plate around
exhaust vent pipe
and seal all edges
with non-flammable
insulation such as
fiberglass, mineral
wool or ceramic.
Do not use high
temperature caulk-
ing materials to seal
any edge to prevent
future serviceability
Check building codes prior to installation.
•
Installation MUST comply with local, regional, state
and national codes and regulations.
•
Consult local building, fire officials or authorities
having jurisdiction about restrictions, installation
inspection, and permits.