Quadra-Fire • QV36DB-A • 2018-900 Rev. F • 12/07
16
V
H
1' MIN. (305mm)
2' MAX. (610mm)
2' MIN. (610mm)
4' MAX. (1.22m)
3' MIN. (914mm)
6' MAX. (1.86m)
4' MIN. (1.22m)
8' MAX. (2.4m)
V+H=40' MAX. (12.4m) H = 8' MAX. (2.4m)
NOTE:
On vertical venting configurations where
the vertical component is over 10 feet install
the vertical baffle included in the manual bag
assembly to improve flame appearance.
Figure 11. Venting with One 90° Elbow
VENTING WITH ONE (1) 90° ELBOW
VENTING WITH ONE (1) 90° ELBOW
V (FT.)
H (FT.)
1' MIN. (305mm)
5' MAX. (1.52m)
2' MIN. (610mm)
10' MAX. (3.1m)
3' MIN. (914mm)
15' MAX. (4.65m)
4' MIN. (1.22m)
20' MAX. (6.2m)
V+H= 40’ MAX. (12.4MM) H = 20' MAX. (6.2m)
Figure 12. Venting with One 90° Elbow
NOTE:
If a 90
o
elbow is
first attached to the unit,
the maximum horizontal
run is 3-feet (914mm).
NOTE:
For corner installations: A 6-inch (152mm)
section of straight pipe may need to be attached to
the fireplace before a 90
o
elbow, to allow the vent
pipe to clear the top standoffs.
V
H
H
V
H
V