August 3, 2015
7063-513E
5
VOYAGEUR
Install Guide
2
Getting Started
A. Design and Installation Considerations
Before installing, determine the following:
• Type of chimney connector to be used
· single wall, 6 inch (152mm) diameter, stainless steel, or
· double wall, 6 inch (152mm) diameter, stainless steel
• Consult page 28 for clearances to combustibles
• Power outlet located close by for optional blower
B. Draft
Draft is the pressure difference needed to vent appliances
successfully. When a appliance is drafting successfully, all
combustion byproducts are exiting the home through the
chimney.
Considerations for successful draft include:
• Preventing negative pressure
• Location of appliance and chimney
To be sure that your appliance burns properly:
• During a low burn, the chimney draft (static pressure) should
be approximately -.04 inch water column (W.C.)
• During a high burn the chimney draft should be approximately
-.10 inch (W.C.)
• Measure the W.C at 6 inches (152mm) above the top of the
appliance after one hour of operation at each burn setting.
NOTICE:
Hearth & Home Technologies assumes no
Check building codes prior to installation.
• Installation MUST comply with local, regional, state and
national codes and regulations.
• Consult insurance carrier, local building, fi re offi cials or
authorities having jurisdiction about restrictions, installation
inspection, and permits.
CAUTION
WARNING
• DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE SERVICING ANOTHER APPLIANCE.
• DO NOT CONNECT TO ANY AIR DISTRIBUTION
DUCT OR SYSTEM.
May allow fl ue gases to enter the house.
Asphyxiation Risk.
• Installation and use of any damaged appliance.
• Modifi cation of the appliance.
• Installation other than as instructed by Hearth & Home
Technologies.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
• Operating appliance without fully assembling all components.
• Operating appliance without legs attached (if supplied with
unit).
• Do NOT Overfi re - If appliance or chimney connector glows,
you are overfi ring.
Any such action that may cause a fi re hazard.
WARNING
Fire Risk.
Hearth & Home Technologies disclaims any
responsibility for, and the warranty will be
voided by, the following actions:
responsibility for the improper performance of the
appliance system caused by:
•
Inadequate draft due to environmental conditions
• Downdrafts
• Tight sealing construction of the structure
• Mechanical exhausting devices
• Overdrafting caused by excessive chimney heights
•
Ideal performance is with height of chimney between
14-16 feet (4.26-4.88m) measured from the base of
the appliance.