background image

13

05/22

8106-803B

C. Negative Pressure

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)
•  Range hoods
• Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or air conditioning
•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

-  Recessed lighting

-  Attic hatch

-  Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

• Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design
•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and seams 

taped or sealed

NOTICE:

  Hearth  &  Home  Technologies  assumes  no 

responsibility for the improper performance of the 

chimney system caused by:

• 

Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

• 

Mechanical exhausting devices

D. Draft

Draft is the pressure difference needed to vent an appliance 

successfully. When an appliance is drafting successfully, all 

combustion byproducts are exiting the home through the 

chimney.

Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:
•  Preventing negative pressure
•  Location of appliance and chimney

NOTE:

 Follow venting manufacturers recommendations 

for sealing pipe joints.

E. Minimum Vacuum Requirements

.075 inches W.C.

F. Chimney and Exhaust Connection

1. 

Chimney & Connector

:  Use  3  or  4  inch  (76-102mm) 

diameter  type  “L”  or  “PL”  venting  system.  It  can  be 

vented vertically or horizontally.

2. 

Mobile Home: 

Approved for all Listed pellet vent. If using 

the 3 inch (76mm) vertical Top Vent Adapter Kit or the 3 

to 6 inch (76-152mm) Top Vent Offset Adapter, use Listed 

double wall flue connector. A Quadra-Fire Outside Air Kit 

must be used with manufactured home installations.

3. 

Residential: 

The  3  inch  (76mm)  vertical  Top  Vent 

Adapter  Kit  and  the  3  to  6  inch  (76-152mm) Top  Vent 

Offset Adapter  are  tested  to  use  24  gauge  single  wall 

flue  connector  or  Listed  double  wall  flue  connector  to 

Class A Listed metal chimneys, or masonry chimneys 

meeting  International  Residential  Code  standards  for 

solid fuel appliances.

4. 

INSTALL VENT AT CLEARANCES SPECIFIED BY 

THE VENT MANUFACTURER.

5. 

Seal exhaust venting system to the appliance with High 

Temp  500ºF  RTV  silicone  sealant.  Secure  the  venting 

system to the appliance with at least (3) screws. All pellet 

vent pipe must be secured together either by means 

provided by the pipe manufacturer or by (3) screws at 

each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST 

VENTING SYSTEM OF THIS Appliance.

7.  DO  NOT  CONNECT  THIS Appliance  TO A  CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

Risk of Asphyxiation! 

Negative pressure can cause spillage of combustion 

fumes and soot.

WARNING

Summary of Contents for OUTFITTER-I

Page 1: ...iquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING Hot glass will cause burns Do not touch glass...

Page 2: ...Getting Started A Design Installation Location Considerations 5 B Thermostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Removal of Appliance from Pallet 6 F Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearances to Combustibles UL and ULC 9 C Hearth Pad Requirements UL and ULC 9 4 Vent Information A Venting Terminatio...

Page 3: ...HHV Tested Efficiency 74 6 EPA BTU Output 6 800 26 000 per hr BTU Input 9 600 to 33 200 per hr Vent Size 3 or 4 Type L or PL Hopper Capacity 60 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using data collected during EPA emissions tests in accordance with the requirements of CSA B415 1 Weighted average HHV High Heating Value efficiency using data collected during...

Page 4: ...Stove Composition These pellet burning stoves are made of steel cast iron or a combination of both with a ceramic viewing glass These stoves incorporate a self feeding system including a fuel storage hopper and a mechanical feed system which is controlled by a micro processing control board Each model contains a variable speed distribution blower to circulate room air through the heat exchanger an...

Page 5: ...Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation on paper using exact measurements for clearances and floor protection before actually beginning the installation Lo...

Page 6: ...Plated surfaces have been wiped clean with a soft cloth if applicable Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Risk of Fire Damaged parts could impair safe operation Do NOT install damaged incomplete...

Page 7: ...ing this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check outlet with multi meter for proper polarity and voltage 115 120 VAC Record voltage reading _____________ ATTENTION INSTALLER Follow this Standard Work Checklist This standard work checklist is to be ...

Page 8: ...06 803B A Appliance Dimensions Figure 8 1 Top View 3 1 2 89mm Figure 8 3 Front View 21 3 4 552mm 33 3 4 858mm 7 7 8 200mm 11 3 8 289mm Figure 8 2 Side View 12 7 8 326mm 22 1 8 562mm 3 3 Dimensions and Clearances ...

Page 9: ...hru 10 4 USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor protection extending beneath the flue pipe is required with horizontal venting or under the Top Vent Adapter with vertical installation D B A Figure 9...

Page 10: ... 42 1067mm 13 58 346mm 24 7 8 632mm USA Figure 10 3 876mm 76mm 1067mm 346mm 632mm Canada Figure 10 4 Fire Risk Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING from side of appliance 2 51mm 25 635mm 28 7 8 733mm 13 5 8 346mm from front of appliance 6 152mm USA Figure 10 1 ...

Page 11: ...P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants wood or any other combus tible 12 in 36 in no OAK Clearance from any forced air intake of other appliance 12 in Clearance horizontally from combustible wall 15 in Vented directly through a wall mini...

Page 12: ...demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house Hearth Home Technologies assumes no responsibility for not does the warranty extend to smoke damage caused by reverse drafting of pellet appliances un...

Page 13: ... Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successful draft include Preventing negative pressure Location of appliance and chimney NOTE Follow venting manufacturers recommendations for sealing pipe joints E Minimum Vacuum Requirements 075 inches W C F Chimney and Exhaus...

Page 14: ...left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe is required Pellet Venting Component of Elbows Feet of Pipe Multiplied By Equivalent Feet Components Equivalent Feet 90 Elbow or Tee ...

Page 15: ...ere passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 Figure 15 1 Straight Out 6 152mm Minimum Non combustible Hearth Pad Wall Thimble Horizontal Termination Cap 2 51mm Minimum 6 152mm Minimum from glass NOTICE Please note that while the minimum clearance for the termination cap is 6 inches 152mm there is the possibility of so...

Page 16: ... from 3 inch 76mm air clearance to no less than 1 inch 25mm air clearance to combustibles for approved Listed pellet pipe Follow pipe manufactures listed air clearances to combustibles and installation instructions for all reduced air clearances installations D Vertical into Existing Class A Chimney C Through The Wall Vertical External Horizontal B Vertical Interior Typical Installation Firestop F...

Page 17: ...ner with Airspace Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of NFPA 211 Factory built chimney must be minimum 6 inch 152mm UL103 HT Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual prov...

Page 18: ...tion cap is 6 inches 152mm there is the possibly of soot build up around the termination area If this occurs we suggest to move the termination further away from the house to prevent it The suggested minimum is 12 inches 6 in 152mm Minimum Non combustible Hearth Pad Wall Thimble Horizontal Termination Cap 2 in 50 8mm Minimum 6 in 152mm Minimum From Glass Straight Out Wall Thimble Illustration show...

Page 19: ...ipe and run pipe through wall 5 Attach flex pipe to outside termination cap with second hose clamp 6 Secure termination cap to outside surface 7 Secure trim ring to interior wall A Outside Air Kit Kit 811 0872 uses a 2 inch flex hose which is included in the kit and uses hose clamps to secure the hose Parts Included in 2 inch Kit 811 0872 1 piece of 2 inch x 3 ft flex hose 2 hose clamps 1 collar a...

Page 20: ...s direct sunlight above a lamp television radiator a wall next to a window or direct heat from the appliance Avoid damp environments as this can lead to corrosion that may shorten thermostat life If painting or construction work around cover the thermostat completely or wait until work is complete before installation 1 Connect your thermostat wire to the W and R terminals Figure 20 1 Figure 20 1 W...

Page 21: ...m Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 7 7 Mobile Home Installation Products of combustion generate carbon monoxide and different fuels generate different levels Carbon monoxide Only use approved fuels in this appliance Always keep door shut during operation Operating this appliance with doors open can allow CO to leak into the home CO can kill you before you are awa...

Page 22: ...22 05 22 8106 803B A Service Maintenance Log Date of Service Performed By Description of Service 8 8 Reference Materials ...

Page 23: ... maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We recommend that you record the following pertinent information for your heating appliance Date purchased installed Serial Number Location on appliance Dealership purchased from Dealer Phone 1 Notes Th...

Reviews: