January 

4, 

2018 

     7082-150C 

       

 

 

 

 

15

MT VERNON E2 INSERT-C

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Example of 3 Elbow-Rear Vent Termination Calculation

Pellet Venting 

Component

# of 

Elbows

Feet of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components

Equivalent Feet

90

o

 Elbow or Tee

3

X

5

15

45

o

 Elbow

X

3

Horizontal Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

Note:  This is a generic example and is not 

intended to represent any specific fuel type.

Vent surfaces get HOT, can cause burns if 

touched.  Non-combustible shielding or guards 

may be required.

WARNING

Figure 15.2

3 in. or 4 in. (76mm or 102mm) Diameter  Pipe 

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET 

20 

30 

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only 

10 

Example 1

Example 2

Example 1

:  If the equivalent length of pipe is 23 feet (7m) with 

altitude of 8,000 feet (2438m) you must use 4 inch (102mm) 

diameter type “L” or “PL” vent.

Example 2

:  If the equivalent length of pipe is 12 feet (3.7m) 

with altitude of 6,000 feet (1829m) you may use 3 or 4 inch 

(76 to 102mm) diameter type “L” or “PL” vent.

G.  Pipe Selection Chart 

The chart will help you in determining proper venting size 

according to the equivalent feet of pipe calculated previously 

and the altitude above sea level of this installation.  

Figure 15.2

a.  Locate the calculated equivalent feet of pipe on the vertical 

left side of the chart.  

b.  Move to the right horizontally on the chart until you reach 

your altitude above sea level.

c.  If you fall below the diagonal line, 3 or 4 inch (76 to 102mm) 

pipe may be used.  

d.  If it is anywhere above the diagonal line, a 4 inch (102mm) 

diameter pipe is required.

NOTICE:

 

•  A 90° elbow is 5 times as restrictive to the flow of exhaust 

gases under positive pressure as 1 foot (305mm) of hori

-

zontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a foot of 

vertical pipe.

WARNING

RISK OF INJURY OR PROPERTY DAMAGE!

•  Improper installation, adjustment, alteration, service or main

-

tenance can cause injury or property damage. 

•  Refer to the owner’s information manual provided with this 

appliance. 

•  For assistance or additional information consult a qualified 

installer, service agency or your dealer.

Risk of Fire!

•    Only LISTED venting components may be used.
•    NO OTHER vent components may be used.
•  Substitute or damaged vent components may impair 

safe operation.

WARNING

Figure 15.1

F.  Equivalent Feet of Pipe 

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent size.  

Figure 15.1.

Summary of Contents for MTVI-E2-CSB-C

Page 1: ...ot store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing...

Page 2: ...Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearance To Combustibles US Canada 8 C Minimum Opening for Masonry Zero Clearance Fireplaces 9 D Hearth Extension 9 E Floo...

Page 3: ...9 Amps Run 2 45 Amps E Mobile Home Approved This appliance is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided The stru...

Page 4: ...of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney of...

Page 5: ...on unless installing into an existing masonry fireplace B Tools And Supplies Needed C Inspect Appliance and Components Open the appliance and remove all the parts and articles packed inside the Compon...

Page 6: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Page 7: ...605mm 26 7 8 in 683mm 11 7 8 in 302mm 24 1 8 in 613mm 33 in 838mm 50 in 1270mm 34 1 2 in 876mm 45 in 1143mm 11 3 4 in 297mm 18 1 2 in 469mm Figure 7 2 Front View with Cast Panel Set 23 7 8 in 606mm 32...

Page 8: ...or choice must be added to this dimension B Clearance To Combustibles US Canada Figure 8 1 Built in Appliance Rear Vent NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONL...

Page 9: ...4 inches Minimum Opening Dimensions Inches Millimeters A Height 24 3 8 619 B Front Width Steel Panel Set 32 1 4 819 Front Width Cast Panel Set 32 1 4 819 C Back Width 24 1 8 613 D Depth Steel Panel Se...

Page 10: ...250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Heath Home Technolog...

Page 11: ...lace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and t...

Page 12: ...lk paved driveway located on public property M 12 in Under an open veranda porch deck or balcony N See Note below Electric service above below or to the side location must not obstruct or interfere wi...

Page 13: ...demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation...

Page 14: ...nstruction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented vertically...

Page 15: ...to the equivalent feet of pipe calculated previously and the altitude above sea level of this installation Figure 15 2 a Locate the calculated equivalent feet of pipe on the vertical left side of the...

Page 16: ...side combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams...

Page 17: ...Air Vertical Figure 17 1 NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insulation such as fiberglass mineral wool or ceramic Do not use high temperature caulking...

Page 18: ...space such as an attic or garage Figure 18 1 Collar Wire Ties Trim Ring Termination Cap 3 inch Aluminum Flex Pipe not included Figure 18 2 OAK Exploded View Lower the leveling bolts if necessary to k...

Page 19: ...cast trim header 2 cast trim footers left and right 1 fastener package Tools Needed Powered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim p...

Page 20: ...crews provided Figure 20 3 Back of Top Surround Back of Side Surround Screws Figure 20 1 Shown with trim installed on panel set G Optional Log Set Placement Instructions 2 PIECE LOG SET INSTALLATION 1...

Page 21: ...e located on an inside wall approximately 5 up from the floor W R Saturday and Sunday can be programmed individually by changing the format from 5 2 to 5 1 1 To change the format 1 Press and hold the...

Page 22: ...ermostat should be located on an inside wall approximately 5 up from the floor PROGRAMMABLE THERMOSTAT PART WALL STAT P W R Saturday and Sunday can be programmed individually by changing the format fr...

Page 23: ...es when burning on high A prop erly adjusted fire will burn cleaner and have higher efficiencies Please copy and paste the follow web address http www quadrafire com Owner Re sources Use and Care Vide...

Page 24: ...4 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 24 1 CAUTION Never draw outsi...

Page 25: ...January 4 2018 7082 150C 25 MT VERNON E2 INSERT C A Service and Maintenance Log Date of Service Performed By Description of Service 8 Reference Materials...

Page 26: ...26 7082 150C January 4 2018 MT VERNON E2 INSERT C Date of Service Performed By Description of Service...

Page 27: ...nly LOGS 60 AE B Y Outside Air Kit OAK 3 Top Vent Adapter TPVNT 4 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim SP MTVS GD Component Pack 7036 042...

Page 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: