9
17 August, 2018
7075-177A
VOYAGEUR GRAND AU
HEARTH EXTENSION
(MINIMUM REQUIREMENT)*
SIDE
TRIM (76mm max depth)
SIDE W
ALL
TOP TRIM (19mm max depth)
572mm
1092mm
1176mm
896mm
HEARTH EXTENSION
(MINIMUM REQUIREMENT)*
FIREPLACE FRONT
SURF
ACE
MANTEL
(305mm max depth)
MANTEL
DEFLECTOR
REQUIRED
1143 mm
572mm
Required Protection
Suggested Protection
NOTE: Keep Ashlip
Clear of Ashes
Figure 9.1
Figure 9.2
Figure 9.3
C
D
A
B
Minimum Opening Dimensions
Millimeters
A
Height
619
B
Front Width
(Steel Surround)
835
Front Width
(Cast Surround)
835
C
Back Width
610
D
Depth
(Steel Surround)
464
Depth
(Cast Surround)
464
NOTE:
If trim measurement is over 19mm in depth use
mantle or side clearances to combustibles.
NOTE:
Minimum opening dimensions include a 6mm
clearance around unit.
Minimal requirement for extension protection*
The hearth thermal protection minimal requirement
is a minimum quantity of 2 -15mm compressed
cement sheets stacked on top of each other with a
thermal conductivity of 0.5 W/m°K.
NOTE:
The fireplace is to be set on a non-combustible
surface.
B. Clearances to Combustibles,