November 29, 2016
7060-228G
9
Explorer III Wood Stove
Fire Risk
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
WARNING
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches (Millimeters)
Note: A, C, and F Dimensions are to the center of the flue collar
EXPLORER-III
INSTALLATION: FULL VERTICAL
A
B
C
D
E
F
G
H*
SINGLE WALL PIPE
10-1/2 (267)
7 (178)
27 (686)
12 (305)
7 (178)
18 (457)
52-1/2 (1334)
N/A
DOUBLE WALL PIPE
9-1/2 (241)
6 (153)
27 (686)
12 (305)
5 (127)
16 (406)
52-1/2 (1334)
N/A
INSTALLATION: 90 DEGREE ELBOW OFF TOP OF APPLIANCE THROUGH BACKWALL
DOUBLE WALL PIPE
9-1/2 (241)
6 (153)
27 (686)
12 (305)
N/A
N/A
52.1/2 (1334)
18 (457)
INSTALLATION: HORIZONTAL THROUGH THE WALL
SINGLE WALL PIPE
N/A
N/A
43-1/2 (1105)
25-1/2 (648)
N/A
N/A
52-1/2 (1334)
N/A
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A
chimney or masonry chimney. Maximum depth of Alcove shall be no more than 48 inches (1219mm) and the referenced alcove
clearances. Canada must comply with
CAN/ULC-S269 M87
for the 650° factory built chimney.
* FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED
BACKWALL / SIDEWALL
B
A
C
D
F
CORNER INSTALLATION
E
G
A
ALCOVE SIDE VIEW
C
ALCOVE TOP VIEW
12 in.
304.8mm
40.5 in.
1029 mm
52.5 in.
1334 mm
MANTEL
12” MAX
HORIZONTAL THROUGH WALL
TOP AND SIDE VIEW
G
H*
APPLIANCE TO
CEILING
CLEARANCE
C. Clearances to Combustibles