15

250-3692 (11/2000)  DVi32 Gas Insert

VERTICAL TERMINATIONS (cont.)
USING GS SERIES PIPE (cont.)

Step 8

. Twist-lock the vent cap and seal.

NOTE:

(1)

For multi-story vertical installations, a ceiling

firestop (SDV part #963) is required at the second
floor, and any subsequent floors (Figure 6). The
opening should be framed to 10” x 10” (254mm x
254mm) inside dimensions.

(2)

Any occupied areas above the first floor, including

closets and storage spaces, which the vertical vent
passed through must be enclosed. The enclosure
may be framed and sheetrocked with standard
construction materials; however, refer to these
installation instructions for the minimum allowable
clearance between the outside of the vent pipe
and the combustible surfaces of the enclosure. Do
not fill any of the required air space with insulation.

INSTALLING INTO AN EXISTING MASONRY OR
FACTORY-BUILT METAL CHIMNEY

(see Masonry Installation Diagram on page 12)

Step 1.

Inspect the chimney to ensure there are no holes,

etc. in structure. Vacuum any ash or dirt from the
fireplace to avoid it being sucked into blower on
stove.

Step 2.

Insert a rope through the end of the flex puller and

tie a knot at the end of the rope. Attach the flex
puller to the flex liner using four sheet metal
screws. Be sure to label one liner “exhaust” and
other “intake”. Carefully feed the liner down the
chimney and out through the damper.

NOTE:

  If additional lengths of flex liner are needed

to span the chimney height, use a flex coupler to
connect the pieces of flex liner together. Connect
the flex to the coupler with four sheet metal screws
on each end.

Step 3.

After carefully feeding the liner down the chimney

to the bottom, line up the flex liner with the vent
opening on the appliance.

NOTE:

  Do not let the flex liner sag below the level

at which it will connect to the appliance. This could
allow hot gas to become trapped and potentially
become a fire hazard. The flex liner path should
always be sloped up toward the termination cap.

Step 4.

Remove the flex puller from the flex liner and

temporarily secure the liner to the top of the
chimney. Be sure to leave 2”-3” (51-76mm) of flex
above the existing chimney to allow for connection
to the top adaptor.

Step 5.

Repeat steps 2-4 for the second length of flex liner,

if applicable.

CEILING FIRESTOP

MINIMUM 1"
CLEARANCE

MINIMUM 1"
CLEARANCE

FIG. 6

MINIMUM 1"
CLEARANCE

NAILS

MINIMUM 1"
CLEARANCE

f i r e - p a r t s . c o m

Summary of Contents for DVI-32

Page 1: ...epartment Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas suppli...

Page 2: ...rocedures 9 Front brick shutoff plate adjustment 9 Gas connections 9 Venting instructions 10 Installation precautions 10 Safety precautions 10 Venting parts list 11 Venting system maintenance 11 Planning your installation 12 Vertical terminations Using GS series pipe 12 Installing into an existing masonry or factory built metal chimney 15 Lighting instructions 17 First fire 18 Maintenance Cleaning...

Page 3: ...N 1 149 This vented gas fireplace is not for use with air filters Install and use only in accordance with manufactaurer s installation and operating instructions Not for use with solid fuel Keep burner and control compartment clean See installation and operating instructions accom panying this appliance Due to high surface temperatures keep children clothing and furniture away ELECTRICAL SUPPLY 12...

Page 4: ...le materials gasoline and other flammable vapors and liquids This appliance is hot during operation and should be located out of heavy traffic areas and away from furniture and draperies Clothing or other flammable material should not be placed on or near the appliance Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ...

Page 5: ... A REGULATOR UPSTREAM FROM THE APPLIANCE IF LINE PRESSURE IS GREATER THAN 1 2 PSIG OUTPUT SIDE TEST PRESSURE INPUT SIDE TEST PRESSURE PRESSURE TESTING If the gas supply piping system exceeds pressures of 1 2 PSIG during testing this appliance and its individual shutoff valve must be disconnected from the piping system If test pressure is less than or equal to 1 2 PSIG then this appliance must be i...

Page 6: ...6 250 3692 11 2000 DVi32 Gas Insert DIMENSIONS 7 1 2 190mm 23 15 16 680mm 12 305mm 29 737mm 30 762mm 30 762mm 14 1 2 368mm 13 13 16 351mm 10 9 16 268mm 11 16 18mm fire parts com ...

Page 7: ...000 over the 2000 level Exception As permitted by the authority having jurisdiction LISTINGS The Quadra Fire DVI 32 is listed to ANSI Z21 88a 1998 CSA 22 33a M98 and CAN1 2 17 M91NFPA 70 by OMNI Test Laboratories Inc Beaverton Oregon CLEARANCES TO COMBUSTIBLES Minimum clearances to combustible materials from stove body A Side wall to combustibles 9 229mm B Height of combustible above bottom of ins...

Page 8: ...Place nuggets in a single layer across the burner tube Make sure that nuggets do not fall behind the tube If more than one layer of nuggets is placed across the burner tube flame impingement and tall sooty flames can result If the flames on one side are too high adjust the nuggets until the flame is the same height on both sides of the stove The log set is installed at the factory To remove log se...

Page 9: ... 2m 20 gauge 25 7 6m 22 gauge 18 5 5m WARNING Do not cut the grounding terminal off under any circumstances Do not route the power cord under the body of the appliance due to high temperatures INSTALLATION PROCEDURES The following procedures show some of the basic installation applications Remember that every installation is different and the installer should adjust to insure that the appliance is...

Page 10: ...ing system installation of any component part not approved by Aladdin Hearth Products or installation other than as instructed by these instructions Consult your local building codes before beginning this installation WARNING Always maintain the required clearances air space to nearby combustibles to avoid creating a fire hazard Do not fill air space with insulation Minimum clearance between vent ...

Page 11: ... 12 12 roof itch 945 45 elbow two maximum 953 Storm collar 963 Ceiling firestop 988 Wall strap 991 High wind termination cap 2280 3 76mm chimney flex liner 923GCL Co linear to co axial adaptor VENTING SYSTEM MAINTENANCE Conduct an inspection of the venting system semiannually Recommended areas to inspect are as follows 1 Check areas of the venting system which are exposed to the elements for corro...

Page 12: ...ero clearance chimney it is important to carefully measure the length of flex needed to reach from the appliance outlet to the termination cap If the flex length is too short a flex coupler will be needed to attach an additional length of flex liner to make up the difference If the flex length is too long the liner could sag below the appliance outlet which could result in a potential fire hazard ...

Page 13: ...tep 4 Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance up through the round support box Insure that all pipe and elbow connections are in their fully twist locked position Step 5 Cut a hole in the roof centered on the small drill hole placed in the roof in step 2 The hole should be of sufficient size to meet the minimum requirements for clearance to combu...

Page 14: ...roofing nails Insure the roofing material overlaps the top edge of the flashing Figure 4 Verify that you have at least the minimum clearance to combustibles at the roofline Step 7 Continue to assemble pipe sections and seal with silicone until the height of the vent cap H Figure 5 meets the minimum building code requirements described in Table 1 Figure 5 and outlined in the current CANGA Bl49 Inst...

Page 15: ...rope through the end of the flex puller and tie a knot at the end of the rope Attach the flex puller to the flex liner using four sheet metal screws Be sure to label one liner exhaust and other intake Carefully feed the liner down the chimney and out through the damper NOTE If additional lengths of flex liner are needed to span the chimney height use a flex coupler to connect the pieces of flex li...

Page 16: ...ap SDV part 991 to the top adaptor see Figure 9 Do not use any other termination cap Step 9 Attach the flex lines to the appliance using hose clamps provided FIG 7 FIG 8 FIG 9 We strongly recommend the use of two flex liners to properly install the DVi 32 NOTE THE FOLLOWING INSTALLATION IS APPROVED FOR APPLICATIONS IN THE UNITED STATES ONLY IT IS NOT APPROVED FOR INSTALLATIONS IN CANADA The DVI 32...

Page 17: ...the left hand side fascia access door to expose the gas control 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 6 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you smell gas STOP Follow B of the safety information above If you don t smell gas go to the next...

Page 18: ...an odor and steam coming from the insert This is normal it is the high temperature paint finishing the curing process Open the door and or windows in the home or structure for ventilation We recommend that you cycle the insert to heat for several minutes until it reaches the curing stage and then turn to off to cool for five minutes Then turn the insert back on and burn until the steam and or odor...

Page 19: ...ing of the stove and it should be checked 4 Check the thermostat and thermopile connections at the valve and tighten or reconnect if needed 5 If the burner still will not ignite you may have a bad valve call your dealer or authorized service person Check the pilot and burner flames periodically When properly adjusted they should look like the flames in the illustration below Call your dealer or au...

Page 20: ...ch as but not limited to blowers wiring thermodisc switches and gas valves are covered by Aladdin s one year warranty program Aladdin Hearth Products will not be responsible for any alteration to the unit which causes sooting that results in damage to the interior of the building in which this appliance is installed This warranty is void if the stove has been operated in atmospheres contaminated b...

Reviews: