7100FP EPA Woodburning Fireplace
A Gas
Termination
Wood or Fuel Oil Termination
B
6
in.
(152 mm) min.
20 in.
(508 mm) min.
Gas, Wood or Fuel
Oil Termination
8 ft
(2.44 m)
(min. for B-Vent)
20 in.
(508 mm)
(min. for direct vent)
to
Perpendicular
Wall
18 in.
(457 mm)
A
Gas
Termination
B
Termination Caps Staggered Height
Figure 26.2 Multiple Chimneys
6
Complete the Enclosure
A. Chimney Termination (2-10-03 Rule)
Chimney Termination Requirements
(See Figures 26.1 and 26.2)
• Must have a cap approved and listed for this fireplace system
• Must not be located where it will become plugged by snow or other material
• Must terminate at least 3 ft (914 mm) above the roof
and
at least 2 ft (610 mm) above any portion of the roof within 10 ft
(3.05 m)
• Must be located away from trees or other structures
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
10 ft. (305cm) To Nearest Roofline
2 ft. (61cm)
Pitched Roof
Flat Roof
10 ft. (305cm) or more
3 ft. (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
Figure 26.1 Termination Requirements